ELE06-01586
| Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 4:36:54 PM | P | PART |
|
|
Requesting an inspection to cover walls.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty elec room walls only ok to cover
|
ELE06-02754
| Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 4:22:32 PM | P | PASS |
|
|
thane; Phone #: ###-#### Note: please 1/2 hr prior to inspection after 4:00 Internet Inspection Request from: Cathy Chiles corr made, ric ok
|
ELE06-03077
| Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 3:41:05 PM | P | FAIL |
|
|
george ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, nec 250.86 metal enclosures shall be grounded, 314.17(C) nm cable shall be stapled within 8" of boxes, 334.80 nm cable shall not be stapled on edge, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) recpts shall be spaced such that no point along the floor line is over 6' from recpt outlet,BCC all make-up shall be done(back recpt), no violations shall be retained,verify room count-12 rooms minimum
|
ELE06-03067
| Temporary Service | 8/18/2006 | 8/18/2006 | 8/18/2006 2:51:30 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s o/h n ok
|
ELE06-03076
| Final | 8/18/2006 | 8/18/2006 | 8/18/2006 2:44:10 PM | P | PASS |
|
|
daryl - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
|
ELE06-02919
| Final | 8/17/2006 | 8/18/2006 | 8/18/2006 11:53:22 AM | A | CANC |
|
|
mitch - another company is finishing the work so this needs to be doc finaled; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, explained that city must have new permit number from new contr prior to final this permit
|
ELE06-03057
| Electrical Rough-In | 8/18/2006 | 8/18/2006 | 8/18/2006 9:29:13 AM | P | PASS |
|
|
brian Note: bob call Cathy Mae 3802 for help if needed; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls only ok to cover
|
ELE06-03062
| Electrical Rough-In | 8/17/2006 | 8/18/2006 | 8/18/2006 9:25:23 AM | A | PASS |
|
|
phil; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok
|
ELE06-02613
| Electrical Rough-In | 8/17/2006 | 8/18/2006 | 8/18/2006 9:23:08 AM | A | PART |
|
|
this for a final on the second floor temporary occupancy, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 2nd floor ok for t/o, signed card, left corr notice BCC need to see partitions and permanent lighting (pendants)
|
ELE06-02989
| Temporary Service | 8/17/2006 | 8/18/2006 | 8/18/2006 8:51:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g n ok
|