Inspections for the day of: Friday, August 18, 2006.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-01586 Electrical Rough-In8/18/20068/18/20068/18/2006 4:36:54 PMPPART
Requesting an inspection to cover walls.; Phone #: ###-#### Internet Inspection Request from: Dan Hardisty elec room walls only ok to cover
ELE06-02754 Electrical Rough-In8/18/20068/18/20068/18/2006 4:22:32 PMPPASS
thane; Phone #: ###-#### Note: please 1/2 hr prior to inspection after 4:00 Internet Inspection Request from: Cathy Chiles corr made, ric ok
ELE06-03077 Electrical Rough-In8/18/20068/18/20068/18/2006 3:41:05 PMPFAIL
george ; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, left corr notice, nec 250.86 metal enclosures shall be grounded, 314.17(C) nm cable shall be stapled within 8" of boxes, 334.80 nm cable shall not be stapled on edge, 300.4(A)&(D) edge of bored holes and nm cable shall be 1 1/4" from edge of framing members, 210.52(A)(1) recpts shall be spaced such that no point along the floor line is over 6' from recpt outlet,BCC all make-up shall be done(back recpt), no violations shall be retained,verify room count-12 rooms minimum
ELE06-03067 Temporary Service8/18/20068/18/20068/18/2006 2:51:30 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Tracy Robertson t/s o/h n ok
ELE06-03076 Final8/18/20068/18/20068/18/2006 2:44:10 PMPPASS
daryl - call for access; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok to final
ELE06-02919 Final8/17/20068/18/20068/18/2006 11:53:22 AMACANC
mitch - another company is finishing the work so this needs to be doc finaled; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley called contr, explained that city must have new permit number from new contr prior to final this permit
ELE06-03057 Electrical Rough-In8/18/20068/18/20068/18/2006 9:29:13 AMPPASS
brian Note: bob call Cathy Mae 3802 for help if needed; Phone #: ###-#### Internet Inspection Request from: Cathy Chiles walls only ok to cover
ELE06-03062 Electrical Rough-In8/17/20068/18/20068/18/2006 9:25:23 AMAPASS
phil; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ric ok
ELE06-02613 Electrical Rough-In8/17/20068/18/20068/18/2006 9:23:08 AMAPART
this for a final on the second floor temporary occupancy, any questions please call James Lingelbaugh; Phone #: ###-#### Internet Inspection Request from: Jeff Radford 2nd floor ok for t/o, signed card, left corr notice BCC need to see partitions and permanent lighting (pendants)
ELE06-02989 Temporary Service8/17/20068/18/20068/18/2006 8:51:19 AMAPASS
Phone #: ###-#### Internet Inspection Request from: William Zerfas t/s u/g n ok