Inspections for the day of: Monday, August 18, 2008.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR06-00527 INSP-Final Inspection8/18/20088/18/20088/18/2008 5:06:11 PMPPASS
Permit finaled.
FIR07-00863 INSP-Final Inspection8/18/20088/18/20088/18/2008 4:51:54 PMPNR
Project is not ready for final inspection, outside waterflow bell must also be functional.
FIR08-00151 INSP-Alarm Testing8/15/20088/18/20088/18/2008 4:49:38 PMPFAIL
Elevator is not yet completed to verify fire alarm interconnections and functionality.
FIR07-00942 INSP-Final Inspection8/18/20088/18/20088/18/2008 4:46:21 PMPPASS
Verified map on site at FACP, NFPA 72's recieved, fire alarm permit finaled.
BLD04-01836 FIRE-Final Inspection8/18/20088/18/20088/18/2008 10:58:00 AMAPASS
Fire life safety finaled.
BLD08-00854 FIRE-Final Inspection8/18/20088/18/20088/18/2008 10:50:57 AMPFAIL
Provide approved hardware at several locations throughout including office and restroom doors, install additonal exit sign/EM light as discussed or provide compliant hardware at the horizontal slider door at the warehouse area.
FIR08-00408 INSP-Final Inspection8/15/20088/18/20088/18/2008 10:46:27 AMAPASS
Field verified noted correction, inspection passed, fire alarm permit finaled.
BLD08-00854 FIRE-Final Inspection8/15/20088/18/20088/18/2008 12:00:00 AMACANC
Larry- fire life safety Phone #: ###-####