FIR08-00699
| INSP-Final Inspection | 8/18/2009 | 8/18/2009 | 8/19/2009 7:22:12 AM | P | PASS |
|
|
Sprinkler monitoring, forward flow, C/N items, final walkthrough passed, contractor to call in UG permit for final as discussed, one missing escutcheon installed while on site, head guards at the mezzanine to be in place prior to building final, unfinished dentist office protected with uprights at the deck and provided with area separation.
|
FIR08-00775
| INSP-Final Inspection | 8/14/2009 | 8/18/2009 | 8/19/2009 7:17:57 AM | A | PART |
|
|
Fire alarm testing for area "B" completed including correction notice items and notification throughout. Correction items from this inspection include two missing smoke detectors at the open junction boxes on the sloped ceiling in the cafeteria, provide notification for the modified floorplan at a classroom area "A" as noted, one SD at the corridor area A north end has not been relocated, switched addresses at two smoke detectors, sprinkler monitoring okayed.
|
BLD09-01365
| FIRE-Final Inspection | 8/18/2009 | 8/18/2009 | 8/18/2009 2:41:27 PM | P | FAIL |
|
|
Fire sprinkler coverage does not meet NFPA 13 standard at two rooms, noted three missing escutcheons, post the fire extinguisher on the wall as indicated-see note #6 on review comments.
|
FIR09-00449
| INSP-Conference | 8/17/2009 | 8/18/2009 | 8/18/2009 10:53:39 AM | A | DONE |
|
|
On site visit regarding underground fire supply line depth of bury and PIV location. Minimum cover of 4' 6" from finish grade to the top of pipe to be maintained per BMC amendments and NFPA 13 guidelines.
|
BLD09-00928
| FIRE-Final Inspection | 8/17/2009 | 8/18/2009 | 8/18/2009 10:50:23 AM | A | PASS |
|
|
Fire life safety inspection completed acceptable including mag lock fail safe at the main entry/exit door.
|
BLD09-00265
| FIRE-Final Inspection | 8/17/2009 | 8/18/2009 | 8/18/2009 10:48:31 AM | A | PASS |
|
|
Noted correction items field verified for completion, fire life safety passed.
|