FIR04-00634
| INSP-Final Inspection | 8/12/2010 | 8/18/2010 | 8/20/2010 11:23:27 AM | A | PASS |
|
|
Permit finaled
|
FIR10-00322
| INSP-Sprinkler Rough-in/Hydro | 8/18/2010 | 8/18/2010 | 8/18/2010 3:14:32 PM | P | PASS |
|
|
The overhead hydro test passed and the remaining sprinkler piping can be covered. One earthquake bracing was not installed but was installed by the end of the hydro test.
|
FIR09-00060
| INSP-Final Inspection | 8/18/2010 | 8/18/2010 | 8/18/2010 3:04:15 PM | P | PASS |
|
|
Permit finaled.
|
FIR09-00060
| FIR-Aging Inspection | 8/18/2010 | 8/18/2010 | 8/18/2010 3:03:23 PM | | PASS |
|
|
|
FIR10-00224
| FIR-Aging Inspection | 8/18/2010 | 8/18/2010 | 8/18/2010 3:00:20 PM | | NR |
|
|
Work is in progress
|
FIR10-00099
| INSP-Final Inspection | 8/16/2010 | 8/18/2010 | 8/18/2010 2:53:51 PM | P | FAIL |
|
|
The technician did not have a monitor to verify the Netcon so no testing was performed. I noted that the duct smoke detectors set the panel into alarm but there are no notification devices. These will need to report as supervisory. Tim and I spoke about getting this changed.
|
BLD10-01273
| FIRE-Final Inspection | 8/17/2010 | 8/18/2010 | 8/18/2010 1:42:06 PM | A | FAIL |
|
|
This inspection was actually a conference for the placement of exit signs and emergency lighting in the warehouse area. The architect provided a stamped plan, which I field approved, for the placement of the new devices. I turned in two copied to tim woodard for our permanant record.
|
FIR10-00287
| INSP-Sprinkler Rough-in | 8/18/2010 | 8/18/2010 | 8/18/2010 1:37:07 PM | P | PASS |
|
|
Underground rough to cover inspection. The underground supply piping is ok to cover. The city approved plans indicate 1 1/4" piping but the contractor has installed 1 1/2".
|
BLD10-01551
| FIRE-Final Inspection | 8/18/2010 | 8/18/2010 | 8/18/2010 10:32:16 AM | P | PASS |
|
|
Life safety passed
|