Inspections for the day of: Tuesday, August 18, 2015.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-00104 ELE-Aging Inspection8/18/20158/18/20158/21/2015 3:32:22 PM CANC
too busy
ELE13-00091 ELE-Aging Inspection8/18/20158/18/20158/21/2015 3:32:03 PM CANC
too busy
ELE12-02275 ELE-Aging Inspection8/18/20158/18/20158/18/2015 3:44:42 PM DONE
Still under construction
ELE12-02903 ELE-Aging Inspection8/18/20158/18/20158/18/2015 3:40:45 PM DONE
Still under construction
ELE15-01320 Final8/18/20158/18/20158/18/2015 3:40:21 PMPPASS
Please call Clay when on way so I can meet you there. Thanks ###-#### Phone #: ###-#### Inspection requested via web by Clay Morgan Final ok
ELE15-02594 Electrical Rough-In8/18/20158/18/20158/18/2015 3:08:47 PMPPASS
rough in and final Phone #: ###-#### Inspection requested via web by Andrea Creek Check left of washer outlet for right of fireplace box. Garage to be done in future. Main bath 2 shower cans and switches rough in ok cover
ELE15-02316 Final8/17/20158/18/20158/18/2015 2:22:04 PMAPASS
Carl Phone #: ###-#### Final ok
ELE15-02316 Electrical Rough-In8/18/20158/18/20158/18/2015 2:21:10 PMPPASS
Carl Phone #: ###-#### Grid rough in ok cover
ELE15-02554 Final8/17/20158/18/20158/18/2015 2:11:38 PMAPASS
Call Williams for access ###-#### Inspection requested via web by jamie berg Final ok
ELE15-01031 Final8/17/20158/18/20158/18/2015 1:43:58 PMAFAIL
Robyn Phone #: ###-#### 210.52(C)(5)- Receptacle outlets that serve counter top shall be located on ar above but not more than 20" above counter top served. 314.20- In wall of tile if box is more than 1/4" recessed in wall a plaster ring or extention ring shall be installed. 334.40- NM cable hanging from soffit shall terminate in a box. 406.9(A)- All 15 or 20 amp receptacle outlets installed outdoors shall be weather resistant type. 406.12- All receptacle outlets installed in or on dwelling unit shall be tamper resistant type. 408.4- Circuit directory shall be completed. 422.30- Appliances shall have a disconnecting means. Water heater and dishwasher shall have a disconnect or lock-out. Called contractor with list of corrections he stated he did not finish job. Informed home owner a permit shall be pulled for trim out
of job.
ELE15-02447 Rough-In Permanent Service8/17/20158/18/20158/18/2015 8:51:28 AMAFAIL
Phone #: ###-#### Inspection requested via web by Lynn Cable Family room NM cable not inside wall. nail plate behind furnace. Verbal with contractor
ELE15-02582 Rough-In Permanent Service8/17/20158/18/20158/18/2015 7:58:17 AMACANC
Phone #: ###-#### Inspection requested via web by Kelly Felin Contractor called and asked to cancel