FIR15-00505
| INSP-Sprinkler Rough-in | 8/17/2015 | 8/18/2015 | 8/18/2015 3:27:54 PM | P | PASS |
|
|
Rough to cover inspection passed/complete, approved for cover.
|
FIR15-00301
| INSP-Final Inspection | 8/18/2015 | 8/18/2015 | 8/18/2015 2:57:02 PM | P | PART |
|
|
Previously noted items not corrected, still need label on door for FACP Room, no document cabinet at FACP and no floor plan with initiating devices posted at FACP
|
BLD15-01595
| FIRE-Final Inspection | 8/18/2015 | 8/18/2015 | 8/18/2015 1:39:39 PM | P | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00462
| INSP-Final Inspection | 8/17/2015 | 8/18/2015 | 8/18/2015 11:24:20 AM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD15-02579
| FIRE-Final Inspection | 8/17/2015 | 8/18/2015 | 8/18/2015 10:11:08 AM | A | FAIL |
|
|
Kitchen hood suppression systems needs inspected/serviced and tagged with a current inspection tag. Fire extinguishers need to be inspected/serviced and tagged with a current inspection tag. Multiple emergency egress lights do not operate with the test button, egress lights need to be repaired/replaced before next inspection. Semi recessed escutcheon missing on fire sprinkler head in kitchen area, needs to be installed. Several concealer escutcheons in south banquet room area are painted, need to be replaced.
|
FIR15-00440
| INSP-Final Inspection | 8/13/2015 | 8/18/2015 | 8/18/2015 10:04:29 AM | A | PASS |
|
|
Fire alarm inspection passed/complete
|
BLD15-00296
| FIRE-Final Inspection | 8/17/2015 | 8/18/2015 | 8/18/2015 10:02:19 AM | A | PASS |
|
|
Life fire safety passed/complete
|
FIR15-00477
| INSP-Final Inspection | 8/17/2015 | 8/18/2015 | 8/18/2015 10:00:10 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|