Inspections for the day of: Thursday, August 18, 2016.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00185 INSP-Final Inspection8/18/20168/18/20168/18/2016 4:53:58 PMPPASS
Previously noted items have been repaired, final fire alarm inspection passed/complete.
FIR15-00836 INSP-Final Inspection8/18/20168/18/20168/18/2016 4:52:52 PMPPASS
Previously noted items have been repaired, ceiling fans that were located to close to smoke detectors have been removed and covers installed over electrical boxes at time of inspection. Flow switch, backlow tamper switches and post indicator valve on fire sprinkler system all tested correctly. Batteries were changed to 7 amp hour batteries to coincide with city approved drawings. Final fire alarm inspection passed/complete.
BLD16-02494 FIRE-Final Inspection8/18/20168/18/20168/18/2016 4:47:03 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers will be mounted in discussed locations, fire extinguishers have current inspection tags, no modifications to commercial equipment so no modifications to commercial hood fire suppression system, commercial hood fire suppression has current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00098 INSP-Supply line flush8/17/20168/18/20168/18/2016 1:39:44 PMADONE
Underground supply main line flush complete
BLD14-03207 FIRE-Final Inspection8/17/20168/18/20168/18/2016 1:19:38 PMAPART
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher is mounted in a path of common travel with a current inspection tag. Final life fire safety inspection for level 10 penthouse and mechanical room passed/complete. Post fire smoke evacuation system needs to be tested/inspected for entire building before core and shell permit can be finaled for life fire safety.
BLD15-02368 FIRE-Final Inspection8/17/20168/18/20168/18/2016 1:16:32 PMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for level 9 complete.
BLD16-02090 FIRE-Final Inspection8/18/20168/18/20168/18/2016 12:17:49 PMPPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguisher are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00536 INSP-Final Inspection8/17/20168/18/20168/18/2016 12:16:04 PMAPASS
Final fire alarm inspection passed/complete.
FIR16-00301 INSP-Final Inspection8/17/20168/18/20168/18/2016 10:58:39 AMAPASS
Final fire alarm communicator inspection passed/complete
FIR16-00300 INSP-Final Inspection8/17/20168/18/20168/18/2016 10:58:12 AMAPASS
Final fire alarm communicator inspection passed/complete
FIR16-00302 INSP-Final Inspection8/17/20168/18/20168/18/2016 10:57:46 AMAPASS
Final fire alarm communicator inspection passed/complete
FIR16-00098 INSP-Sprinkler Rough-in/Hydro8/17/20168/18/20168/18/2016 10:06:33 AMAPASS
200 psi hydrostatic test complete for underground supply
BLD15-01919 FIRE-Final Inspection8/18/20168/18/20168/18/2016 7:14:24 AMAPASS
Fire sprinkler inspection complete, fire alarm inspection complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
BLD16-02487 FIRE-Final Inspection8/16/20168/18/20168/18/2016 6:49:00 AMAPASS
No fire sprinkler modifications, fire alarm inspection is complete, fire extinguishers are in common area's with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00516 INSP-Final Inspection8/16/20168/18/20168/18/2016 6:47:54 AMAPASS
Final fire alarm inspection passed/complete