Inspections for the day of: Friday, August 18, 2017.
Number of inspections: 8
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJames Ady
TitleELE-INSPECTOR
Phone #914-4683
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02842 ELE-Aging Inspection8/18/20178/18/20178/18/2017 1:48:18 PM DONE
Neil will look into it and call for final
ELE17-02662 Electrical Rough-In8/18/20178/18/20178/18/2017 1:45:26 PMPPASS
contact is Dan, Underground in warehouse area Phone #: ###-#### Inspection requested via web by Lori Stout Underground in warehouse only ok to cover
ELE17-02523 Electrical Rough-In8/18/20178/18/20178/18/2017 1:44:50 PMPPASS
Phone #: ###-#### Inspection requested via web by steve sellers Garage only ok to cover
ELE17-02156 Final8/17/20178/18/20178/18/2017 11:20:46 AMPPASS
Phone #: ###-#### Inspection requested via web by Ryan Wake Floor heat only final ok
ELE17-00341 Final8/17/20178/18/20178/18/2017 11:20:10 AMAFAIL
Phone #: ###-#### Inspection requested via web by Ryan Wake 210.52 A 2 (1) Fixed panels shall count as wall space. ( need recep right side of back slider fixed panel and right side of Front room fixed panel. 410.16. Recessed lighting in cloths closet shall have enclosed lamp.(laundry room closet. 210.70 A 3. Equipment rooms shall have lighting outlet.(Garage furnace room) 406.6 Receps and switches shall have cover plates installed. 110.3 B Listed equipment shall be installed per manufacturers specs.( Garage 3way locked out)
ELE17-02693 Conference8/17/20178/18/20178/18/2017 9:38:43 AMAPASS
Tim Phone #: ###-#### Talked about Grounding requirments, Sub panel ground seperation and need to update Range and Dryer circuits if 3 wire.
ELE17-00828 Final8/17/20178/18/20178/18/2017 8:33:03 AMAPASS
Remaining final for downstairs apts at building 511. Meet at Primary Office. Contact here is either Todd or Rick. Phone #: ###-#### Inspection requested via web by Todd Sellman Final ok
MIS17-00263 ELE-Conference8/17/20178/18/20178/17/2017 10:52:16 AMADONE
building in back yard with no permits-neighbor says it''s over 200 sq ft not meeting setbacks-also doing electrical work-if have questions call neighor at ###-#### Jennifer Spoke with Jennifer. Informed her no ELE permit was needed as the lights were Low voltage plug in. Let her know there was no violation. Could be a planning and zoning issue.