FIR17-00436
| INSP-Final Inspection | 8/15/2017 | 8/18/2017 | 8/18/2017 1:31:52 PM | P | FAIL |
|
|
No inspection performed. Need appliances installed to verify gas shut off. It appears the wrong nozzle is installed over where the range will be. Also the hood is very narrow and may not come out the 6" beyond the cooking surface.
|
FIR14-00205
| INSP-Sprinkler Rough-in | 8/17/2017 | 8/18/2017 | 8/18/2017 1:28:21 PM | A | PASS |
|
|
Finished the piping rough-in inspection today. As-builts are needed showing all of the new upright coverage in the combustible concealed space above the Foyer. An additional upright head is required near a duct and another upright raised to with-in 12" of the deck.
|
BLD17-02600
| FIRE-Final Inspection | 8/11/2017 | 8/18/2017 | 8/18/2017 11:29:46 AM | A | PASS |
|
|
Life safety passed
|
BLD16-01525
| FIRE-Final Inspection | 8/18/2017 | 8/18/2017 | 8/18/2017 10:24:51 AM | P | FAIL |
|
|
Provide single action hardware for the interior doors, provide tagged/mounted fire entinguishers as discussed and marked on the plans. Provide fire dept. signage as discussed.
Doug Phone #: ###-####
|
BLD17-02740
| FIRE-Final Inspection | 8/17/2017 | 8/18/2017 | 8/18/2017 9:37:41 AM | A | PASS |
|
|
Life safety passed. No racking is currently in the space. Annual sprinkler inspeciton is current.
|
NAF17-00041
| INSP-Sprinkler Rough-in | 8/18/2017 | 8/18/2017 | 8/18/2017 8:21:34 AM | P | PART |
|
|
Tenting passed and wet system piping rough-in passed. Piping can be covered as marked on the city approved plans. Will need another cover inspection once the two tie -ins are complete. Phone #: ###-#### Inspection requested via web by Sam Ball
|
NAF17-00052
| INSP-Sprinkler Rough-in | 8/17/2017 | 8/18/2017 | 8/18/2017 8:01:23 AM | A | CANC |
|
|
Tenting Phone #: ###-#### Inspection requested via web by Sam Ball
|
BLD17-01848
| FIRE-Final Inspection | 8/17/2017 | 8/18/2017 | 8/18/2017 7:38:52 AM | A | PASS |
|
|
Life safety passed
|