Inspections for the day of: Tuesday, August 19, 2003.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR02-00311 INSP-Final Inspection8/18/20038/19/20038/19/2003 12:00:00 AMAFAIL
JIM; Phone #: ###-#### Various hangers on the 2 1/2" branchlines in the warehouse exceed exception #2 of NFPA 13 6-4.5.3 and therefore require E.Q. brace. Provide fourway bracing at all risers per NFPA 13 6-4.5.5. Provide forward flow flush. Walk thru entire project to verify follow up notes and canopies. Verify all review notes have been followed. Provide signage and stripping for FDC access per conversation 8/19/2003 1:31:36 PM
FIR03-00206 INSP-Sprinkler Rough-in8/18/20038/19/20038/19/2003 12:00:00 AMPPART
See approved job site plans for areas with deficencies 8/19/2003 4:10:12 PM
FIR03-00081 INSP-Sprinkler Rough-in/Hydro8/18/20038/19/20038/19/2003 12:00:00 AMPFAIL
No items on the correction notice have been completed. The insulation contractor blew in the attic insulation with out tenting the sprinkler piping. Shilo to provide up to date cpvc sprinkler pipe hanger data 8/19/2003 3:42:58 PM
BLD03-00706 FIRE-Supply Line Cover8/19/20038/19/20038/19/2003 12:00:00 AMPFAIL
BRUCE; Phone #: ###-#### Underground supply piping for the overhead sprinkler system has been installed in an open trench. There are no FIR permits for this project. I contacted bill alexander and left a correction notice that no work was to be continued and that the pipe is not to be covered or it will need to be dug back up. I spoke to Bruce and John with Commercial Fire and they stated that they were not aware that a permit was required for the underground work. 8/19/2003 1:34:35 PM