Inspections for the day of: Thursday, August 19, 2004.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR04-00273 INSP-Final Inspection8/19/20048/19/20048/20/2004 12:00:00 AMPPASS
please call 30 mins prior to inspection///alex ###-####
BLD04-01049 FIRE-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMAPASS
Fire life safety finaled 8/19/2004 8:12:33 AM
BLD04-01082 FIRE-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMAPASS
fire life safety finaled 8/19/2004 7:36:35 AM
BLD04-00850 FIRE-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMAFAIL
Provide sticker at the main entry/exit. Provide emergency lights in stairwells and warehouse areas. Remove door hardware from the store front doors in the warehouse. Provide suite numbers. Test exit signs in the warehouse when emergency lighting is provided. 8/19/2004 11:46:49 AM
FIR04-00484 INSP-Sprinkler Rough-in8/18/20048/19/20048/19/2004 12:00:00 AMAPASS
submit updated plans showing modifications. Sprinkler piping through garage is not installed yet. Piping in main house and tenting is ok. Ok to cover. 8/19/2004 11:40:40 AM
BLD04-01020 FIRE-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMAPASS
fire life safety finaled 8/19/2004 10:45:48 AM
FIR04-00420 INSP-Final Inspection8/19/20048/19/20048/19/2004 12:00:00 AMAPASS
permit finaled
FIR04-00366 INSP-Final Inspection8/19/20048/19/20048/19/2004 12:00:00 AMAPASS
fire alarm finaled
FIR04-00485 INSP-Final Inspection8/19/20048/19/20048/19/2004 12:00:00 AMAPASS
Hood suppression system operated correctly. The appliances are on site but not all of them had been placed under the hood.
BLD04-01104 FIRE-Final Inspection8/19/20048/19/20048/19/2004 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 8/19/2004 at 10:08:33 AM. Contact: ###-####.
FIR03-00453 INSP-Final Inspection8/19/20048/19/20048/19/2004 12:00:00 AMPPART
Still need to test sprinkler risers, door closures, duct detectors and hood system 8/19/2004 4:24:18 PM
BLD04-00086 FIRE-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMPPASS
fire life safety finaled 8/19/2004 2:30:06 PM
FIR01-00436 INSP-Final Inspection8/18/20048/19/20048/19/2004 12:00:00 AMPPART
BRAIN; Phone #: ###-#### Internet Inspection Request from: Annette Moore

Completed elevator testing on North and South elevators; acceptable per the drawings.

Completed sprinkler testing on fire pump, Dry System A and Dry System B; acceptable per the drawings.

Left to test:

All existing kitchen hoods (less Gino's Pizzeria and Creapery).
Center elevator, controls being installed on Friday 8/20/2004.
HVAC shutdown system for Gino's Pizzeria.