Inspections for the day of: Friday, August 19, 2005.
Number of inspections: 16
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBill VanDegrift
TitlePLM-INSPECTOR
Phone #794-9372
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
PLM05-02876 Water and/or Sewer8/19/20058/19/20058/19/2005 2:53:30 PMPPART
Will be ready for an inspection @ 2pm - I have lot 5 block 2 for this house - on line is says lot 11 block 0 and I'm not sure why. If you have any questions please call me sewer only###-#### thank you!!; Phone #: ###-#### Internet Inspection Request from: Holly Ryska
MEC05-02023 Rough-in8/18/20058/19/20058/19/2005 2:36:38 PMAFAIL
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson provide 1" clearance on both fire place flues. provide clearance and hang water heater B-vent. seal kitchen exhaust duct. update fixture count on permit. seal return air duct by furnace. use metal duct for makeup air to mech room. called their office with the last correction because I forgot to include it on the correction notice.
PLM05-01619 Final8/19/20058/19/20058/19/2005 2:27:57 PMPPASS
brett ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie final ok
PLM05-02929 Plumbing Rough-in8/19/20058/19/20058/19/2005 2:12:36 PMPPASS
This will be ready this afternoon. If any question call Russell ###-#### or ###-#### and ask for Laurie in Service.; Phone #: ###-#### Internet Inspection Request from: Sonja Hankel ri ok
PLM05-00549 Water and/or Sewer8/18/20058/19/20058/19/2005 1:56:57 PMAPASS
1:30 sewer ok
PLM05-02850 Water and/or Sewer8/18/20058/19/20058/19/2005 1:21:18 PMAPASS
water tie in water service sewer service and waste repipe ok
MEC05-02613 Rough-in8/17/20058/19/20058/19/2005 12:53:57 PMAFAIL
cheryl; Phone #: ###-#### Internet Inspection Request from: Barbara Moore still has screws in the flue. $42 reinspection fee.
MEC05-02023 Pressure Test8/18/20058/19/20058/19/2005 11:54:56 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Jennifer Jenson gas test ok
PLM05-01707 Final8/18/20058/19/20058/19/2005 10:57:50 AMAPASS
craig ; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
PLM05-02912 Sprinkler (Final)8/18/20058/19/20058/19/2005 10:57:26 AMAPASS
###-#### - chad
PLM05-02874 Water and/or Sewer8/16/20058/19/20058/19/2005 9:50:44 AMAPASS
pat ###-#### water service final ok
PLM05-02664 Final8/18/20058/19/20058/19/2005 9:33:22 AMAPART
Ready first thing Friday morning. lb; Phone #: ###-#### Internet Inspection Request from: Sonja Hankel temp occ ok test dcva and install heater in water heater dog house.
PLM05-02878 Plumbing Rough-in8/18/20058/19/20058/19/2005 9:13:15 AMPPASS
rick; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa ri ok
PLM05-00704 Med/Gas Systems8/18/20058/19/20058/19/2005 8:58:34 AMAPART
On site contact Frank @ ###-####; Phone #: ###-#### underground med gas to scanner. 150 psi test.
PLM05-02874 Final8/19/20058/19/20058/19/2005 12:00:00 AMPPASS
pat ###-####
PLM05-02850 Final8/19/20058/19/20058/19/2005 12:00:00 AMPPASS
water tie in