Inspections for the day of: Friday, August 19, 2005.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorPat Lass
TitleELE-INSPECTOR
Phone #794-9478
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE05-02193 Temporary Service8/19/20058/19/20058/19/2005 3:59:28 PMPFAIL
heidi; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
No electrode at building
seal-offs not poured
open wiring in class one area and not 8 ft above roof
light not approved for class 1 location
ELE05-02797 Electrical Rough-In8/19/20058/19/20058/19/2005 3:09:11 PMPPASS
andy; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE04-03145 Final8/19/20058/19/20058/19/2005 2:58:48 PMPPASS
call if need access//william; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa
ELE05-02324 Final8/19/20058/19/20058/19/2005 2:45:40 PMPFAIL
for hot tub-- carl; Phone #: ###-#### Internet Inspection Request from: Marsha Smylie
bond water and install GFCI recep within20 ft
ELE05-03048 Electrical Rough-In8/19/20058/19/20058/19/2005 2:28:00 PMPPART
Scheduled by a contractor via Hello! on 8/19/2005 at 9:14:13 AM. Contact: ###-####.
walls ok 2nd floor T/I
ELE05-02217 Electrical Rough-In8/19/20058/19/20058/19/2005 2:14:20 PMPPART
CONTACT: LYLE DEAN; Phone #: ###-#### Internet Inspection Request from: Deb McCoy
anop
ELE05-03037 Final8/19/20058/19/20058/19/2005 1:31:09 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Dana Moyer
ELE05-03045 Temporary Service8/18/20058/19/20058/19/2005 11:07:06 AMAFAIL
###-#### - brian
no electrode
no ID
No MBJ
dirty meter
ELE05-02749 Electrical Rough-In8/18/20058/19/20058/19/2005 10:00:00 AMAPART
exterior wall rough-in @ Comstock. Please contact Tom, thank you.; Phone #: ###-#### Internet Inspection Request from: Wendy Waters
3rd floor outside walls ok
ELE05-02214 Rough-In Permanent Service8/19/20058/19/20058/19/2005 9:44:13 AMAPART
Phone #: ###-#### Internet Inspection Request from: Kathy Briggs
1st floor r/i ok
service grounding and bonding not right
ELE05-02169 Rough-In Permanent Service8/18/20058/19/20058/19/2005 9:13:12 AMANR
Please inspect apartments 1,2,3 & 4.; Phone #: ###-#### Internet Inspection Request from: Latisha Peltier
called contractor and will set up conf next week. no print
ELE05-02705 Conference8/18/20058/19/20058/19/2005 8:37:32 AMAPART
###-#### - dale Note: please call 1/2 hr prior to inpsection
talked about upstairs bed room circuiting location of recepa and free conductors
ELE05-00877 ELE-Aging Inspection8/19/20058/19/20058/19/2005 7:43:59 AM PASS
ELE05-00868 ELE-Aging Inspection8/19/20058/19/20058/19/2005 7:42:19 AM DONE
ELE05-00868 DOC - Permit Finaled8/19/20058/19/20058/19/2005 12:00:00 AMPPASS
ELE05-00877 DOC - Permit Finaled8/19/20058/19/20058/19/2005 12:00:00 AMPPASS
ELE05-01751 DOC - Permit Finaled8/19/20058/19/20058/19/2005 12:00:00 AMPPASS