ELE05-02183
| Final | 8/19/2005 | 8/19/2005 | 8/19/2005 4:24:11 PM | P | PASS |
|
|
tim; Phone #: ###-#### Internet Inspection Request from: Barbara Moore ok to final
|
ELE05-01399
| Electrical Rough-In | 8/18/2005 | 8/19/2005 | 8/19/2005 4:23:31 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/18/2005 at 3:20:33 PM. Contact: ###-####. ok to cover ceiling, tails for office furniture ok 3 places
|
ELE05-03039
| Temporary Service | 8/18/2005 | 8/19/2005 | 8/19/2005 2:49:43 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Barbara Szurgot called contr about abrasion prot for gec. t/s u/g n ok
|
ELE05-03041
| Electrical Rough-In | 8/18/2005 | 8/19/2005 | 8/19/2005 1:44:18 PM | P | PASS |
|
|
###-#### - henry met elect, left survey,210.52 (D) recpt shall be within 3' of bath basin,314.17(C) nm shall be stapled within 8" of box, 334.30 nm cable shall be stapled within 12" of box, ric ok
|
ELE05-03051
| Electrical Rough-In | 8/19/2005 | 8/19/2005 | 8/19/2005 10:42:59 AM | P | CANC |
|
|
mike-- ###-#### Inspection cancelled from web by: Marsha Smylie
|
ELE03-03037
| Final | 8/18/2005 | 8/19/2005 | 8/19/2005 10:41:42 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 8/18/2005 at 2:53:09 PM. Contact: ###-####. checked main control room, j-b0xes, added items to fix: 430.102(B) disconnects shall be in sight of motors,352.30(A) rnc shall be supported within 3' of cnd body, need to see cable tray and 3rd party eval needs to commence. will be called back next week.
|
ELE05-01396
| Final | 8/18/2005 | 8/19/2005 | 8/19/2005 9:15:50 AM | A | CANC |
|
|
lynn or mike ###-####///please call when on way to meet; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa called contr about straps and clearance. ok to final
|
ELE05-01346
| Final | 8/18/2005 | 8/19/2005 | 8/19/2005 8:57:13 AM | A | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/18/2005 at 12:14:25 PM. Contact: ###-####. told contr, left corr notice,605.3 wireways shall be free of projections that may damage conductor insulation(power, comm),605.4 partitions shall be connrcted with strain relief, 605.2(B) all nec articles apply and shall be adhered to(close openings,secure covers,provide plates for conduit fittings, comm. protection)
|
ELE05-02586
| Final | 8/18/2005 | 8/19/2005 | 8/19/2005 8:34:44 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Kristopher wilson corrections made, ok to final
|
ELE04-02516
| Final | 8/18/2005 | 8/19/2005 | 8/19/2005 12:00:00 AM | P | CANC |
|
|
please call 15 min prior///mike; Phone #: ###-#### Internet Inspection Request from: Letitia Mesa///cancelled per michael already talked to Bob//8/19/05 LEM 2:17pm
|