FIR05-00266
| INSP-Sprinkler Rough-in | 8/16/2005 | 8/17/2005 | | A | |
|
|
###-#### - bruce Note: after morning 9:00 ish
|
BLD03-02192
| FIRE-Final Inspection | 8/19/2005 | 8/19/2005 | 8/19/2005 3:58:34 PM | P | FAIL |
|
|
Exit discharge lights at two separate areas failed to operate under backup power source.
|
FIR05-00457
| INSP-Final Inspection | 8/19/2005 | 8/19/2005 | 8/19/2005 3:56:08 PM | P | PASS |
|
|
Fire sprinkler finaled.
|
FIR03-00740
| INSP-Final Inspection | 8/18/2005 | 8/19/2005 | 8/19/2005 1:48:20 PM | A | PASS |
|
|
Fire alarm passed inspection.
|
FIR04-00764
| INSP-Final Inspection | 8/18/2005 | 8/19/2005 | 8/19/2005 12:05:23 PM | A | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD05-01626
| FIRE-Final Inspection | 8/18/2005 | 8/19/2005 | 8/19/2005 12:04:13 PM | A | PASS |
|
|
Fire life safety passed inspection.
|
FIR05-00392
| INSP-Final Inspection | 8/19/2005 | 8/19/2005 | 8/19/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled.
|
FIR05-00378
| INSP-Sprinkler Rough-in | 8/19/2005 | 8/19/2005 | 8/19/2005 12:00:00 AM | A | PART |
|
|
Rough-in areas above hard lids are okay to cover, need to cut head in southwest soffit as discussed, GC to provide drop ceiling in storage room, antifreeze system is not complete or inspected at this time.
|