ELE08-02251
| Electrical Rough-In | 8/18/2008 | 8/19/2008 | 8/20/2008 7:19:14 AM | A | PASS |
|
|
Please inspect shop addition. Breaker feeding shop is located at meter base. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS u/g ok to cover, ric ok, called contractor to add 2nd ground rod, said will check at final, check breaker at house for feeder to shop at final, and isolate neutral and grounds in shop panel
|
ESC08-00313
| General Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 4:08:31 PM | P | PART |
|
|
looked ok
|
ELE08-02114
| Rough-In Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 4:07:45 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, this job already done
|
ESC08-00687
| General Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 4:05:27 PM | P | PART |
|
|
looked ok
|
ESC08-00320
| General Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 3:20:52 PM | P | PART |
|
|
looked ok
|
ESC08-00597
| General Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 2:51:40 PM | A | PART |
|
|
looked ok
|
ELE08-02312
| Conference | 8/19/2008 | 8/19/2008 | 8/19/2008 2:12:41 PM | P | DONE |
|
|
talked about when to call for inspection, what inspector will look for, circuiting for fireplace removal, kitchen remodel and spacing of receptacles, number of small appliance branch circuits
|
ELE08-02233
| Rough-In Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 1:48:21 PM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri and p/s
|
ELE08-02233
| Electrical Rough-In | 8/19/2008 | 8/19/2008 | 8/19/2008 1:48:02 PM | P | FAIL |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, left correction notice, NEC 210.52(A) shall provide receptacles in wall space over 2' - entry, back of room, 334.30 nm cable shall not be stapled on edge, 300.4(A) edge of bored holes shall be 1 1/4" from face of framing members or protected by steel plates, BCC shall provide boxes for cables, shall have approved plans on job
|
ELE08-02233
| Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 1:13:25 PM | P | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s u/g n ok, check for intersystem bonding bar at final
|
ELE08-02306
| Rough-In Permanent Service | 8/19/2008 | 8/19/2008 | 8/19/2008 12:17:03 PM | P | PASS |
|
|
allen/wife ###-#### home - if possible after lunch Phone #: ###-#### ri ok p/s u/g rec ok
|
ELE08-00871
| Electrical Rough-In | 8/18/2008 | 8/19/2008 | 8/19/2008 10:30:18 AM | A | PASS |
|
|
leonard Phone #: ###-#### met owner, ric ok, check for bath and kitchen outlet spacing on peninsula bar at final, no esc this project
|
ELE08-01156
| Permanent Service | 8/18/2008 | 8/19/2008 | 8/19/2008 9:42:09 AM | A | FAIL |
|
|
inspection on new meter pack and panels, please call George @ ###-#### to set time to meet and walk thru with Phone #: ###-#### Internet Inspection Request from: Andy Rose met contractor, NEC 310.8(D)(1) conductors shall be listed as being sunlight resistant for overhead service, rest ok for service only, will do each unit one by one for subpanels and inspections, no esc this project
|
ELE08-02259
| Permanent Service | 8/18/2008 | 8/19/2008 | 8/19/2008 8:02:21 AM | A | PASS |
|
|
ron - as early as possible please Phone #: ###-#### p/s, u/g, exst pedestal, rec ok, no esc this project
|
ELE08-02320
| Final | 8/19/2008 | 8/19/2008 | 8/19/2008 12:00:00 AM | P | CANC |
|
|
FINAL INSPECTION REQUESTED FOR SUB PUMP AND MOTOR INSTALL. CALL GENE @ ###-#### WITH STATUS. Phone #: ###-#### Internet Inspection Request from: Gary Coonse
|