Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-02251 Electrical Rough-In8/18/20088/19/20088/20/2008 7:19:14 AMAPASS
Please inspect shop addition. Breaker feeding shop is located at meter base. Thanks Phone #: ###-#### Internet Inspection Request from: ERIC CENTERS u/g ok to cover, ric ok, called contractor to add 2nd ground rod, said will check at final, check breaker at house for feeder to shop at final, and isolate neutral and grounds in shop panel
ESC08-00313 General Inspection8/19/20088/19/20088/19/2008 4:08:31 PMPPART
looked ok
ELE08-02114 Rough-In Permanent Service8/19/20088/19/20088/19/2008 4:07:45 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, this job already done
ESC08-00687 General Inspection8/19/20088/19/20088/19/2008 4:05:27 PMPPART
looked ok
ESC08-00320 General Inspection8/19/20088/19/20088/19/2008 3:20:52 PMPPART
looked ok
ESC08-00597 General Inspection8/19/20088/19/20088/19/2008 2:51:40 PMAPART
looked ok
ELE08-02312 Conference8/19/20088/19/20088/19/2008 2:12:41 PMPDONE
talked about when to call for inspection, what inspector will look for, circuiting for fireplace removal, kitchen remodel and spacing of receptacles, number of small appliance branch circuits
ELE08-02233 Rough-In Permanent Service8/19/20088/19/20088/19/2008 1:48:21 PMPCANC
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson see ri and p/s
ELE08-02233 Electrical Rough-In8/19/20088/19/20088/19/2008 1:48:02 PMPFAIL
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson called, left message, left correction notice, NEC 210.52(A) shall provide receptacles in wall space over 2' - entry, back of room, 334.30 nm cable shall not be stapled on edge, 300.4(A) edge of bored holes shall be 1 1/4" from face of framing members or protected by steel plates, BCC shall provide boxes for cables, shall have approved plans on job
ELE08-02233 Permanent Service8/19/20088/19/20088/19/2008 1:13:25 PMPPASS
Phone #: ###-#### Internet Inspection Request from: Therrin Robertson p/s u/g n ok, check for intersystem bonding bar at final
ELE08-02306 Rough-In Permanent Service8/19/20088/19/20088/19/2008 12:17:03 PMPPASS
allen/wife ###-#### home - if possible after lunch Phone #: ###-#### ri ok p/s u/g rec ok
ELE08-00871 Electrical Rough-In8/18/20088/19/20088/19/2008 10:30:18 AMAPASS
leonard Phone #: ###-#### met owner, ric ok, check for bath and kitchen outlet spacing on peninsula bar at final, no esc this project
ELE08-01156 Permanent Service8/18/20088/19/20088/19/2008 9:42:09 AMAFAIL
inspection on new meter pack and panels, please call George @ ###-#### to set time to meet and walk thru with Phone #: ###-#### Internet Inspection Request from: Andy Rose met contractor, NEC 310.8(D)(1) conductors shall be listed as being sunlight resistant for overhead service, rest ok for service only, will do each unit one by one for subpanels and inspections, no esc this project
ELE08-02259 Permanent Service8/18/20088/19/20088/19/2008 8:02:21 AMAPASS
ron - as early as possible please Phone #: ###-#### p/s, u/g, exst pedestal, rec ok, no esc this project
ELE08-02320 Final8/19/20088/19/20088/19/2008 12:00:00 AMPCANC
FINAL INSPECTION REQUESTED FOR SUB PUMP AND MOTOR INSTALL. CALL GENE @ ###-#### WITH STATUS. Phone #: ###-#### Internet Inspection Request from: Gary Coonse