Inspections for the day of: Tuesday, August 19, 2008.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00905 INSP-Supply line flush8/19/20088/19/20088/20/2008 1:33:26 PMPCANC
Per Roy a flush will not be performed until the parking lot pavement is done.
BLD08-01770 FIRE-Final Inspection8/19/20088/19/20088/19/2008 4:24:09 PMPPART
A temporary occupancy was given until emergency lighting is provided in all paths of egress and the thumbturn locks have been replace with single action hardware on the two north exit doors.
FIR08-00060 INSP-Final Inspection8/18/20088/19/20088/19/2008 4:17:02 PMAPASS
Permit finaled
BLD08-00498 FIRE-Final Inspection8/19/20088/19/20088/19/2008 2:57:04 PMPPASS
Life safety passed. The fire alarm system modifications as required by this permit has been installed under a separate permit number.
FIR08-00560 INSP-Sprinkler Rough-in/Hydro8/18/20088/19/20088/19/2008 2:56:03 PMAFAIL
Additional upright protection is required along the duct work in the south restroom. The north restroom is ok to cover.
BLD08-00436 FIRE-Final Inspection8/18/20088/19/20088/19/2008 1:45:57 PMAPASS
Life safety passed. Sprinkler modifications not required per letter from American Fire Protection
FIR08-00045 INSP-Sprinkler Rough-in/Hydro8/18/20088/19/20088/19/2008 12:36:08 PMAFAIL
Resubmittals are needed showing the upright heads being changed to pendant heads, added upright heads in the daycare/remote area, and all of the added pendants in the closets. The entire space above the ceiling, in the daycare, will need to be covered with sprinklers or a code based solution provided. Access shall be provided to view the dry upright sprinkler heads. The uprights have been deleted from the corridors but there is exposed wood above the ceilings in the corridors. Reducing fittings have been used and are not allowed per NFPA 13 unless the exception is met.
FIR06-00204 INSP-Final Inspection8/14/20088/19/20088/19/2008 12:27:08 PMAPASS
Permit finaled. Hood suppression system operated correctly.
FIR08-00473 INSP-Final Inspection8/18/20088/19/20088/19/2008 12:22:41 PMAFAIL
New electrical conduit is blocking pendant sprinkler heads. The sprinkler system annual inspection has expired.
BLD08-00193 FIRE-Final Inspection8/18/20088/19/20088/19/2008 10:11:04 AMAPASS
Life safety passed