FIR07-00905
| INSP-Supply line flush | 8/19/2008 | 8/19/2008 | 8/20/2008 1:33:26 PM | P | CANC |
|
|
Per Roy a flush will not be performed until the parking lot pavement is done.
|
BLD08-01770
| FIRE-Final Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 4:24:09 PM | P | PART |
|
|
A temporary occupancy was given until emergency lighting is provided in all paths of egress and the thumbturn locks have been replace with single action hardware on the two north exit doors.
|
FIR08-00060
| INSP-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 4:17:02 PM | A | PASS |
|
|
Permit finaled
|
BLD08-00498
| FIRE-Final Inspection | 8/19/2008 | 8/19/2008 | 8/19/2008 2:57:04 PM | P | PASS |
|
|
Life safety passed. The fire alarm system modifications as required by this permit has been installed under a separate permit number.
|
FIR08-00560
| INSP-Sprinkler Rough-in/Hydro | 8/18/2008 | 8/19/2008 | 8/19/2008 2:56:03 PM | A | FAIL |
|
|
Additional upright protection is required along the duct work in the south restroom. The north restroom is ok to cover.
|
BLD08-00436
| FIRE-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 1:45:57 PM | A | PASS |
|
|
Life safety passed. Sprinkler modifications not required per letter from American Fire Protection
|
FIR08-00045
| INSP-Sprinkler Rough-in/Hydro | 8/18/2008 | 8/19/2008 | 8/19/2008 12:36:08 PM | A | FAIL |
|
|
Resubmittals are needed showing the upright heads being changed to pendant heads, added upright heads in the daycare/remote area, and all of the added pendants in the closets. The entire space above the ceiling, in the daycare, will need to be covered with sprinklers or a code based solution provided. Access shall be provided to view the dry upright sprinkler heads. The uprights have been deleted from the corridors but there is exposed wood above the ceilings in the corridors. Reducing fittings have been used and are not allowed per NFPA 13 unless the exception is met.
|
FIR06-00204
| INSP-Final Inspection | 8/14/2008 | 8/19/2008 | 8/19/2008 12:27:08 PM | A | PASS |
|
|
Permit finaled. Hood suppression system operated correctly.
|
FIR08-00473
| INSP-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 12:22:41 PM | A | FAIL |
|
|
New electrical conduit is blocking pendant sprinkler heads. The sprinkler system annual inspection has expired.
|
BLD08-00193
| FIRE-Final Inspection | 8/18/2008 | 8/19/2008 | 8/19/2008 10:11:04 AM | A | PASS |
|
|
Life safety passed
|