ESC07-00876
| General Inspection | 8/19/2009 | 8/19/2009 | 8/19/2009 4:31:29 PM | P | PASS |
|
|
looked ok
|
ELE08-03233
| Final | 8/19/2009 | 8/19/2009 | 8/19/2009 4:27:27 PM | P | PART |
|
|
This inspection will be for the engine room. Contact is Rey. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw 412 and 370 did inspection for this area and other response on 8-5-09, still need locknuts, bushings,conduit strapping, covers and drains installed, condulets closed, ko seals for areas for the engine room, will call for inspection for tomorrow for coreections for disconnect at switchgear area
|
ELE09-00946
| Electrical Rough-In | 8/19/2009 | 8/19/2009 | 8/19/2009 4:00:14 PM | P | PASS |
|
|
This inspection will be for a wall rough-in. contact is Rey. Thank you and have a great day. Phone #: ###-#### Internet Inspection Request from: Laura Longshaw walls and hard lids only ok to cover, 412 and 370 did inspesction as before for p/s
|
ELE09-01511
| Permanent Service | 8/19/2009 | 8/19/2009 | 8/19/2009 3:13:56 PM | P | PASS |
|
|
Contact Jerry Palmer for instructions. Phone #: ###-#### Internet Inspection Request from: Tina Payne p/s o/h rec ok, no esc this project
|
ELE09-01527
| Temporary Service | 8/19/2009 | 8/19/2009 | 8/19/2009 2:52:58 PM | P | CANC |
|
|
Dennis Phone #: ###-#### see conference
|
ELE09-01527
| Conference | 8/19/2009 | 8/19/2009 | 8/19/2009 1:22:18 PM | P | DONE |
|
|
Dennis Phone #: ###-#### called contractor, told to provide access to ground rod, move loose wire out of meter socket, provide abrasion protection for gec, add w/p receptacles, no esc this project
|
ELE09-01349
| Final | 8/18/2009 | 8/19/2009 | 8/19/2009 1:18:51 PM | P | PART |
|
|
cust is finishing the basement. Phone #: ###-#### Internet Inspection Request from: Stephen Kren owner taken receptacle faces off to trim, loose receptacles, dead circuits, called, left message to call when finished, no esc this project
|
ELE09-01522
| Conference | 8/18/2009 | 8/19/2009 | 8/19/2009 9:51:53 AM | A | DONE |
|
|
Jay Phone #: ###-#### met contractor and owner, reviewed service change and sub-panels, inspection request, left correction for owner NEC 110.26 sufficient access and working space shall be provided and maintained about all electrical equipment, 230.70(A)(!) service disconnecting means shall be installed at a readily accessible location outside of a building, 230.6(2) conductors shall be considered outside of building where installed in raceway encased in not less than 2" of concrete- owner asked for tis correction notice for his own sake, talked about derating conductors, conduit fill, j-boxes, grounding, mast height, no esc this project
|
ELE08-00407
| Electrical Rough-In | 8/18/2009 | 8/19/2009 | 8/19/2009 8:53:20 AM | A | PART |
|
|
Joe Phone #: ###-#### walls only ok to cover anop
|
ELE09-01517
| Electrical Rough-In | 8/18/2009 | 8/19/2009 | 8/18/2009 6:51:47 PM | A | CANC |
|
|
Internet Inspection Request from: BARRY KENDALL Inspection cancelled from web by: BARRY KENDALL
|