Inspections for the day of: Wednesday, August 19, 2009.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00290 INSP-Final Inspection8/18/20098/19/20098/20/2009 8:08:06 AMAPART
Inspection for riser supervision completed at the remainder of systems on the south side of the building through riser room #4 with the exception of solenoid operation at the interlock/vesda and low air supervisory signals at riser 2 and 4, pre-testing/adjustments done while on site, panel trouble conditions also cleared while waiting on site, one flow switch at freezer system 27 failed to operate. Will test the remainder of sprinkler system monitoring as discussed. Per contractor, WP appliances at the wet produce racks have been installed, open circuts at nac 1,2, and 3 also cleared while on site. Note: during testing a main panel ground fault condition occured.
FIR09-00033 INSP-Alarm Testing8/19/20098/19/20098/20/2009 8:01:13 AMPPART
Inspection for riser supervision completed at the remainder of systems on the south side of the building through riser room #4 with the exception of solenoid operation at the interlock/vesda and low air supervisory signals at riser 2 and 4, pre-testing/adjustments done while on site, panel trouble conditions also cleared while waiting on site, one flow switch at freezer system 27 failed to operate. Will test the remainder of sprinkler system monitoring as discussed.
FIR09-00033 INSP-Sprinkler Rough-in8/14/20098/19/20098/20/2009 7:48:59 AMAFAIL
Inspection for the class IIIB liquid storage racks system failed due to field installation discrepancies with the approved design layout including head spacing and gridded piping at some locations, also noted missing solid shelving between levels above the forklift aisles. Note: Hydrostatic testing completed- however will need to be redone due to pending modifications for this system.
FIR08-00775 INSP-Final Inspection8/14/20098/19/20098/20/2009 7:38:59 AMAPART
See comments per inspection completed by S. Cobbley including areas A, B, D, correction items and adjustments to date.
FIR09-00315 INSP-Final Inspection8/18/20098/19/20098/20/2009 7:35:20 AMAPASS
Scope of fire sprinkler modifications completed acceptable, permit finaled.
FIR09-00421 INSP-Final Inspection8/18/20098/19/20098/20/2009 7:33:57 AMAPASS
Fire sprinkler permit work passed field inspection, permit finaled.
FIR09-00261 INSP-Sprinkler Rough-in8/18/20098/19/20098/20/2009 7:33:02 AMAPART
See approved plan set for red line annotations marked with today's date at two rooms including the restroom and electrical rooms okayed for ceiling cover.
FIR08-00631 INSP-Final Inspection8/18/20098/19/20098/19/2009 10:13:31 AMAPASS
Underground fire supply line permit work approved for final status.
BLD07-02483 FIRE-Final Inspection8/18/20098/19/20098/19/2009 10:12:21 AMAPASS
Life safety completed acceptable, inspection passed.