BLD11-00573
| FIRE-Final Inspection | 8/19/2011 | 8/19/2011 | 8/26/2011 4:55:12 PM | P | DONE |
|
|
|
BLD11-01865
| FIRE-Final Inspection | 8/19/2011 | 8/19/2011 | 8/19/2011 5:11:26 PM | P | CANC |
|
|
Overbooked
|
BLD11-01456
| FIRE-Final Inspection | 8/19/2011 | 8/19/2011 | 8/19/2011 5:08:46 PM | P | PASS |
|
|
Life safety inspection for the scope of permit work completed acceptable.
|
FIR11-00159
| INSP-Final Inspection | 8/19/2011 | 8/19/2011 | 8/19/2011 5:07:34 PM | P | CANC |
|
|
Overbooked
|
FIR11-00334
| INSP-Sprinkler Rough-in/Hydro | 8/18/2011 | 8/19/2011 | 8/19/2011 5:07:17 PM | P | CANC |
|
|
Overbooked
|
FIR11-00412
| INSP-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 5:06:52 PM | P | CANC |
|
|
Overbooked
|
FIR11-00098
| INSP-Final Inspection | 8/19/2011 | 8/19/2011 | 8/19/2011 5:06:30 PM | P | CANC |
|
|
Overbooked
|
FIR11-00221
| INSP-Supply line flush | 8/19/2011 | 8/19/2011 | 8/19/2011 5:05:59 PM | P | PART |
|
|
UG fire supply line flush completed satisfactory.
|
BLD11-00416
| BLD-Conference | 8/19/2011 | 8/19/2011 | 8/19/2011 5:04:42 PM | P | DONE |
|
|
john Phone #: ###-####,, 1:30 pm if possible * NOTE: On site conference completed by S. Arellano.
|
BLD11-01344
| FIRE-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 5:03:31 PM | P | DONE |
|
|
Troy Phone #: ###-####
|
FIR11-00415
| INSP-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 5:03:03 PM | P | CANC |
|
|
Overbooked
|
FIR11-00139
| INSP-Final Inspection | 8/17/2011 | 8/19/2011 | 8/19/2011 5:02:43 PM | A | CANC |
|
|
Overbooked
|
FIR11-00026
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 5:01:48 PM | A | PART |
|
|
Completed remainder of acceptance testing for the new system. Final pending installation and testing of the new IP-DACT per approved plan.
|
BLD10-01853
| FIRE-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 5:00:13 PM | A | NR |
|
|
Final pending project related fire alarm and sprinkler permit finals. Also noted missing exit signs at the 2nd and 3rd floors, need to add discharge lighting at the south exit, discussed project schedule.
|
FIR10-00540
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:57:54 PM | A | PART |
|
|
Items which remain for final include; ceilings at the bike and storage rooms- remove travel caps and install escutcheons on sw heads, remove thermal elements at the four deluge heads on the 1st floor, missing escutcheon at the 3rd floor, noted one closet at AV 222 missing coverage.
|
FIR10-00473
| INSP-Final Inspection | 8/19/2011 | 8/19/2011 | 8/19/2011 4:53:56 PM | A | PASS |
|
|
UG fire supply line permit finaled.
|
FIR10-00293
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:53:17 PM | A | NR |
|
|
Phone #: ###-#### >> Inspection requested via web by Tyler Bowen
|
FIR10-00467
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:52:48 PM | A | FAIL |
|
|
Floor plan and design layout matches the demo sheet- see A2.0 for new floorplan and room designation, incorrect cd settings at two locations including the conference and open office area, provide plans reflecting the added notification device, one-line etc.
|
FIR11-00411
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:47:02 PM | A | PASS |
|
|
Scope of work completed, fire sprinkler permit finaled.
|
FIR11-00411
| INSP-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 4:46:00 PM | P | PART |
|
|
Overhead fire sprinkler work okayed for cover at the drop ceilings.
|
BLD11-01344
| FIRE-Sprinkler Rough-in | 8/19/2011 | 8/19/2011 | 8/19/2011 4:45:04 PM | A | NR |
|
|
Inspection for new heads at the sheetrock ceiling servery entry area- noted new partition and doors not yet installed may create overspacing at adjacent pendents. Project lacks fire sprinkler plans including shop drawings at this time.
|
FIR10-00346
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:40:33 PM | A | FAIL |
|
|
Began testing at the high school brick building address 5493 and modulars #1 and #2. Noted corrections include items on review notes # 7, 20, 25 and 13.
|
FIR11-00213
| INSP-Final Inspection | 8/18/2011 | 8/19/2011 | 8/19/2011 4:36:03 PM | A | PASS |
|
|
Fire alarm permit final approved.
|