Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00339 INSP-Sprinkler Rough-in8/16/20138/19/20138/19/2013 8:27:46 PMPCANC
Rescheduled for tomorrow morning
BLD13-01702 FIRE-Final Inspection8/19/20138/19/20138/19/2013 3:59:12 PMPFAIL
Life saafety will be ok to pass when the project related fire alarm permit is finaled.
FIR13-00182 INSP-Alarm Testing8/14/20138/19/20138/19/2013 3:50:57 PMACANC
To be rescheduled per Brian for thursday.
FIR13-00391 INSP-Final Inspection8/16/20138/19/20138/19/2013 3:47:44 PMAFAIL
Waiting for map at facp and verification that the lightning suppression is not required.
FIR12-00610 INSP-Sprinkler Rough-in8/16/20138/19/20138/19/2013 12:38:50 PMAPART
Piping can be covered but several locations marked in red have upright sprinkler coverage overspaced due to insulation. Also several of the classroom closets have surface mounted light fixtures located right next to sprinkler heads. Ceiling tile will need to be removed to verify these corrections.
FIR13-00392 INSP-Sprinkler Rough-in8/16/20138/19/20138/19/2013 12:36:26 PMAPASS
rough to cover passed. Piping is ok to cover.