Inspections for the day of: Wednesday, August 19, 2015.
Number of inspections: 18
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR15-00216 INSP-Sprinkler Rough-in8/19/20158/19/20158/19/2015 3:16:26 PMPFAIL
Tenting failed in the southeast apartment second floor at the top of the stairs.
BLD14-03486 FIRE-Final Inspection8/19/20158/19/20158/19/2015 3:09:38 PMPFAIL
1) Breakroom 108 exit has been moved from interior doors to exterior door. Need approval with the 118 person occupant load.
2) Provide emergnecy light in Fire Pump Rm
3)Repair Emergency Lights in Locker Rms.
4) Provide signage at Fire Pump Rm.
5) Provide exit discharge lighting without photo cells and timers per discussion.
BLD14-02926 FIRE-Final Inspection8/19/20158/19/20158/19/2015 3:05:02 PMPFAIL
Fire life safety will be ok to pass when the project related fire alarm and fire sprinkler permits are finaled
BLD14-02396 FIRE-Final Inspection8/19/20158/19/20158/19/2015 3:02:40 PMPFAIL
Provide fire dept access signage as per note #12. All other items appear ok.
FIR15-00222 INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015 12:58:27 PMAPASS
Overhead hydro test passed
FIR15-00223 INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015 12:57:54 PMAPASS
Overhead hydro test passed
FIR15-00495 INSP-Final Inspection8/19/20158/19/20158/19/2015 11:27:11 AMPPASS
Permit finaled
FIR14-00475 INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015 10:58:59 AMAPASS
Overhead hydro passed for the second floor
BLD15-00289 FIRE-Final Inspection8/19/20158/19/20158/19/2015 9:31:08 AMPPASS
Life safety passed
FIR15-00538 INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015 9:17:54 AMAPASS
Underground supply piping is ok to cover. I noted that some of the pipe runs are short in distance and United Water supplied stub-in is only at 36" below finish grade.
FIR15-00537 INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015 9:17:24 AMAPASS
Underground supply piping is ok to cover. I noted that some of the pipe runs are short in distance and United Water supplied stub-in is only at 36" below finish grade.
FIR15-00533 INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015 9:16:56 AMAPASS
Underground supply piping is ok to cover. I noted that some of the pipe runs are short in distance and United Water supplied stub-in is only at 36" below finish grade.
FIR15-00536 INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015 9:16:27 AMAPASS
Underground supply piping is ok to cover. I noted that some of the pipe runs are short in distance and United Water supplied stub-in is only at 36" below finish grade.
FIR15-00535 INSP-Sprinkler Rough-in8/18/20158/19/20158/19/2015 9:15:51 AMAPASS
Underground supply piping is ok to cover. I noted that some of the pipe runs are short in distance and United Water supplied stub-in is only at 36" below finish grade.
FIR15-00470 INSP-Final Inspection8/18/20158/19/20158/19/2015 8:11:16 AMAPASS
permit finaled
FIR15-00468 INSP-Final Inspection8/18/20158/19/20158/19/2015 8:04:47 AMAPASS
Permit finaled
BLD15-00788 FIRE-Final Inspection8/18/20158/19/20158/19/2015 7:27:14 AMAPASS
Life safety passed
FIR15-00467 INSP-Sprinkler Rough-in/Hydro8/18/20158/19/20158/19/2015 12:00:00 AMACANC
Troy, We would like to schedule this for late morning if at all possible. Thank you. Jason ###-####. Phone #: ###-#### >> Inspection requested via web by Jason Minnick