BLD15-01107
| FIRE-Final Inspection | 8/19/2016 | 8/19/2016 | 8/19/2016 5:32:07 PM | P | PASS |
|
|
No fire sprinklers in clubhouse, fire alarm inspection for clubhouse complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for clubhouse passed/complete.
|
BLD15-01112
| FIRE-Final Inspection | 8/18/2016 | 8/19/2016 | 8/19/2016 5:27:18 PM | A | FAIL |
|
|
Need to have fire sprinkler and fire alarm permits finaled, apartments need to have suite identification installed.
|
FIR16-00028
| INSP-Final Inspection | 8/19/2016 | 8/19/2016 | 8/19/2016 5:25:23 PM | P | FAIL |
|
|
Need ball drip on FDC piping in riser room. Backflow needs tamper switches installed. FDC needs caps.
|
FIR16-00380
| INSP-Final Inspection | 8/19/2016 | 8/19/2016 | 8/19/2016 5:24:15 PM | P | PASS |
|
|
Final fire alarm inspection passed/complete for clubhouse.
|
FIR16-00414
| INSP-Final Inspection | 8/18/2016 | 8/19/2016 | 8/19/2016 1:13:46 PM | A | PASS |
|
|
Notated city approved drawings with red ink area's inspected. City approved drawings show stairs being installed next to cooler, stairs are not installed and there is no confirmed date for when the stairs will be installed, as-builts will be notated. Final fire sprinkler inspection passed/complete
|
FIR16-00152
| INSP-Final Inspection | 8/18/2016 | 8/19/2016 | 8/19/2016 12:10:36 PM | A | PASS |
|
|
Previously noted items have been repaired, 200 psi hydrostatic test for overhead fire sprinklers piping is complete. Final fire sprinkler inspection passed/complete.
|
FIR16-00101
| INSP-Sprinkler Rough-in | 8/16/2016 | 8/19/2016 | 8/19/2016 11:13:34 AM | A | PART |
|
|
Rough to cover inspection for overhead fire sprinkler piping complete for rooms on levels 3, 4, and 5. Overhead fire sprinkler piping located in rooms on level 3 and 4 approved for cover, overhead fire sprinkler piping on level 5 needs to have tenting insulation installed and inspected before cover can be approved.
|
FIR16-00520
| INSP-Sprinkler Rough-in | 8/18/2016 | 8/19/2016 | 8/19/2016 10:49:03 AM | A | FAIL |
|
|
Rough to cover inspection complete, if no other walls/lintel are installed for the breakroom then small room rule does not apply, fire sprinkler are 8ft off of wall. Office on southside of tenant space has heads 9ft 6in off of wall, small room rule can apply to these heads but max distance is 9ft off of one wall.
|
FIR15-00304
| INSP-Sprinkler Rough-in/Hydro | 8/18/2016 | 8/19/2016 | 8/19/2016 10:05:25 AM | A | PASS |
|
|
200 psi hydrostatic test for level 2 complete . Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, overhead fire sprinkler piping located on level 2 approved for cover.
|
BLD14-03207
| FIRE-Final Inspection | 8/18/2016 | 8/19/2016 | 8/19/2016 9:21:49 AM | A | PART |
|
|
Inspection is for temporary bike storage located at the northeast corner of level 1, no fire sprinkler modifications needed, fire alarm modifications will be notated on as-builds on the fire alarm plans, fire extinguisher is in place with a current inspection tag. Final life fire safety for temporary bike storage passed/complete.
|