Inspections for the day of: Friday, August 19, 2016.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD15-01107 FIRE-Final Inspection8/19/20168/19/20168/19/2016 5:32:07 PMPPASS
No fire sprinklers in clubhouse, fire alarm inspection for clubhouse complete, fire extinguishers are in place with current inspection tags. Final life fire safety inspection for clubhouse passed/complete.
BLD15-01112 FIRE-Final Inspection8/18/20168/19/20168/19/2016 5:27:18 PMAFAIL
Need to have fire sprinkler and fire alarm permits finaled, apartments need to have suite identification installed.
FIR16-00028 INSP-Final Inspection8/19/20168/19/20168/19/2016 5:25:23 PMPFAIL
Need ball drip on FDC piping in riser room. Backflow needs tamper switches installed. FDC needs caps.
FIR16-00380 INSP-Final Inspection8/19/20168/19/20168/19/2016 5:24:15 PMPPASS
Final fire alarm inspection passed/complete for clubhouse.
FIR16-00414 INSP-Final Inspection8/18/20168/19/20168/19/2016 1:13:46 PMAPASS
Notated city approved drawings with red ink area's inspected. City approved drawings show stairs being installed next to cooler, stairs are not installed and there is no confirmed date for when the stairs will be installed, as-builts will be notated. Final fire sprinkler inspection passed/complete
FIR16-00152 INSP-Final Inspection8/18/20168/19/20168/19/2016 12:10:36 PMAPASS
Previously noted items have been repaired, 200 psi hydrostatic test for overhead fire sprinklers piping is complete. Final fire sprinkler inspection passed/complete.
FIR16-00101 INSP-Sprinkler Rough-in8/16/20168/19/20168/19/2016 11:13:34 AMAPART
Rough to cover inspection for overhead fire sprinkler piping complete for rooms on levels 3, 4, and 5. Overhead fire sprinkler piping located in rooms on level 3 and 4 approved for cover, overhead fire sprinkler piping on level 5 needs to have tenting insulation installed and inspected before cover can be approved.
FIR16-00520 INSP-Sprinkler Rough-in8/18/20168/19/20168/19/2016 10:49:03 AMAFAIL
Rough to cover inspection complete, if no other walls/lintel are installed for the breakroom then small room rule does not apply, fire sprinkler are 8ft off of wall. Office on southside of tenant space has heads 9ft 6in off of wall, small room rule can apply to these heads but max distance is 9ft off of one wall.
FIR15-00304 INSP-Sprinkler Rough-in/Hydro8/18/20168/19/20168/19/2016 10:05:25 AMAPASS
200 psi hydrostatic test for level 2 complete . Rough to cover inspection for overhead fire sprinkler piping on level 2 complete, overhead fire sprinkler piping located on level 2 approved for cover.
BLD14-03207 FIRE-Final Inspection8/18/20168/19/20168/19/2016 9:21:49 AMAPART
Inspection is for temporary bike storage located at the northeast corner of level 1, no fire sprinkler modifications needed, fire alarm modifications will be notated on as-builds on the fire alarm plans, fire extinguisher is in place with a current inspection tag. Final life fire safety for temporary bike storage passed/complete.