Inspections for the day of: Monday, August 19, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01403 Electrical Rough-In8/19/20198/19/20198/19/2019 3:01:07 PMPPASS
Concrete pour 1B of Garage level. Phone #: ###-#### Inspection requested via web by Tom Betty Slab pour noted rough in ok cover
ELE19-02109 Final8/19/20198/19/20198/19/2019 2:27:46 PMPPASS
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk
Final ok
ELE19-03089 Temporary Service8/19/20198/19/20198/19/2019 1:57:15 PMPFAIL
Phone #: ###-#### Inspection requested via web by Bob Glenn
110.26- Minimum work space depth shall be provided for temp service. Need at least 36" depth.
ELE19-02904 Permanent Service8/19/20198/19/20198/19/2019 1:46:47 PMPPASS
22k rated main, contractor did not know available fault current at time of inspection. Due to distance to transformer believe we should be ok. Will verify at final. p/s u/g n ok
ELE19-02904 Final8/17/20198/19/20198/19/2019 1:45:47 PMANR
Please call Marcus Phone #: ###-#### Inspection requested via web by Kevin Perez
22k rated main, contractor did not know available fault current at time of inspection. Due to distance to transformer believe we should be ok. Will verify at final.
ELE19-03032 Electrical Rough-In8/16/20198/19/20198/19/2019 10:42:28 AMAPASS
Homeowner should be home. If you have any questions please feel free to contact Andrew ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Clayton Morgan Patio cover rough in ok cover
ELE19-02109 Final8/16/20198/19/20198/19/2019 10:09:42 AMAFAIL
Garage code 1957 Phone #: ###-#### Inspection requested via web by Alan Lusk
210.8- Main bath GFCI device will not set. Unable to test.
ELE19-02909 Permanent Service8/17/20198/19/20198/19/2019 9:50:29 AMAPASS
Phone #: ###-#### Inspection requested via web by ERIC CENTERS
p/s u/g n ok
ELE19-02028 Electrical Rough-In8/16/20198/19/20198/19/2019 9:32:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Grid complete. Rough in ok cover
ELE19-00631 Permanent Service8/18/20198/19/20198/19/2019 9:04:19 AMAPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton
250.24(A)(1)- Concrete encased grounding electrode conductor to be relocated to same terminal or bus grounded conductor is terminated.
250.52(B)(3)- Underground metal gas piping shall not be used as a grounding electrode.
250.104(B)- Bonding of gas piping needed if likely to become energized.
House panel ok p/s u/g n ok