ELE19-01403
| Electrical Rough-In | 8/19/2019 | 8/19/2019 | 8/19/2019 3:01:07 PM | P | PASS |
|
|
Concrete pour 1B of Garage level. Phone #: ###-#### Inspection requested via web by Tom Betty Slab pour noted rough in ok cover
|
ELE19-02109
| Final | 8/19/2019 | 8/19/2019 | 8/19/2019 2:27:46 PM | P | PASS |
|
|
garage code 1957e Phone #: ###-#### Inspection requested via web by Alan Lusk Final ok
|
ELE19-03089
| Temporary Service | 8/19/2019 | 8/19/2019 | 8/19/2019 1:57:15 PM | P | FAIL |
|
|
Phone #: ###-#### Inspection requested via web by Bob Glenn 110.26- Minimum work space depth shall be provided for temp service. Need at least 36" depth.
|
ELE19-02904
| Permanent Service | 8/19/2019 | 8/19/2019 | 8/19/2019 1:46:47 PM | P | PASS |
|
|
22k rated main, contractor did not know available fault current at time of inspection. Due to distance to transformer believe we should be ok. Will verify at final. p/s u/g n ok
|
ELE19-02904
| Final | 8/17/2019 | 8/19/2019 | 8/19/2019 1:45:47 PM | A | NR |
|
|
Please call Marcus Phone #: ###-#### Inspection requested via web by Kevin Perez 22k rated main, contractor did not know available fault current at time of inspection. Due to distance to transformer believe we should be ok. Will verify at final.
|
ELE19-03032
| Electrical Rough-In | 8/16/2019 | 8/19/2019 | 8/19/2019 10:42:28 AM | A | PASS |
|
|
Homeowner should be home. If you have any questions please feel free to contact Andrew ###-####. Thanks! Phone #: ###-#### Inspection requested via web by Clayton Morgan Patio cover rough in ok cover
|
ELE19-02109
| Final | 8/16/2019 | 8/19/2019 | 8/19/2019 10:09:42 AM | A | FAIL |
|
|
Garage code 1957 Phone #: ###-#### Inspection requested via web by Alan Lusk 210.8- Main bath GFCI device will not set. Unable to test.
|
ELE19-02909
| Permanent Service | 8/17/2019 | 8/19/2019 | 8/19/2019 9:50:29 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by ERIC CENTERS p/s u/g n ok
|
ELE19-02028
| Electrical Rough-In | 8/16/2019 | 8/19/2019 | 8/19/2019 9:32:58 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton Grid complete. Rough in ok cover
|
ELE19-00631
| Permanent Service | 8/18/2019 | 8/19/2019 | 8/19/2019 9:04:19 AM | A | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 250.24(A)(1)- Concrete encased grounding electrode conductor to be relocated to same terminal or bus grounded conductor is terminated. 250.52(B)(3)- Underground metal gas piping shall not be used as a grounding electrode. 250.104(B)- Bonding of gas piping needed if likely to become energized. House panel ok p/s u/g n ok
|