Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD05-01306 FIRE-Final Inspection8/2/20058/2/20058/2/2005 4:14:51 PMPPASS
Life safety passed inspection.
BLD05-01671 FIRE-Final Inspection8/1/20058/2/20058/2/2005 2:12:51 PMAFAIL
Repair exit sign (failure to illuminate under backup power source), provide approved door hardware at the main entry/exit door to tenant space-manual thumbturn is not allowed, provide one 2A10BC fire extinguisher within tenant space along a normal path of travel with current inspection tag and the handle mounted no higher than 48" AFF, provide emergency light at hallway adjacent to the break room.
FIR05-00417 INSP-Final Inspection8/2/20058/2/20058/2/2005 12:00:00 AMAPASS
Fire sprinkler passed inspection.
FIR05-00408 INSP-Final Inspection8/2/20058/2/20058/2/2005 12:00:00 AMAPASS
Fire sprinkler finaled.
BLD04-02876 FIRE-Conference8/2/20058/2/20058/2/2005 12:00:00 AMADONE
On site discussion with Wil Northup and Bill Alexander regarding the installation of an above ground water storage tank for supplemental fire sprinkler supply. The tank was installed without an FIR permit and thus not reviewed or approved for code compliance. The general and subcontractors involved were made aware of the situation.