BLD05-01306
| FIRE-Final Inspection | 8/2/2005 | 8/2/2005 | 8/2/2005 4:14:51 PM | P | PASS |
|
|
Life safety passed inspection.
|
BLD05-01671
| FIRE-Final Inspection | 8/1/2005 | 8/2/2005 | 8/2/2005 2:12:51 PM | A | FAIL |
|
|
Repair exit sign (failure to illuminate under backup power source), provide approved door hardware at the main entry/exit door to tenant space-manual thumbturn is not allowed, provide one 2A10BC fire extinguisher within tenant space along a normal path of travel with current inspection tag and the handle mounted no higher than 48" AFF, provide emergency light at hallway adjacent to the break room.
|
FIR05-00417
| INSP-Final Inspection | 8/2/2005 | 8/2/2005 | 8/2/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler passed inspection.
|
FIR05-00408
| INSP-Final Inspection | 8/2/2005 | 8/2/2005 | 8/2/2005 12:00:00 AM | A | PASS |
|
|
Fire sprinkler finaled.
|
BLD04-02876
| FIRE-Conference | 8/2/2005 | 8/2/2005 | 8/2/2005 12:00:00 AM | A | DONE |
|
|
On site discussion with Wil Northup and Bill Alexander regarding the installation of an above ground water storage tank for supplemental fire sprinkler supply. The tank was installed without an FIR permit and thus not reviewed or approved for code compliance. The general and subcontractors involved were made aware of the situation.
|