Inspections for the day of: Wednesday, August 2, 2006.
Number of inspections: 17
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE06-00460 Electrical Rough-In8/2/20068/2/20068/2/2006 4:53:03 PMPPART
Duke, needs a conference with you on this job, please; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt
N & S soffits west end ok
ELE06-02069 Electrical Rough-In8/2/20068/2/20068/2/2006 4:36:58 PMPPART
Scheduled by a contractor via Hello! on 8/2/2006 at 8:41:18 AM. Contact: ###-####. remove cords used for fixed wiring above fish tanks (lighting), support ceiling fans in country store to structure or use listed fan box, conveyor motors only have backwards R U, bond H & C at fish tank W H,and use box extention r/i ok anop
ELE06-02069 Final8/2/20068/2/20068/2/2006 4:31:55 PMPPART
Scheduled by a contractor via Hello! on 8/2/2006 at 8:41:18 AM. Contact: ###-####. anop
ELE05-04071 Electrical Rough-In8/1/20068/2/20068/2/2006 3:16:48 PMAPART
Scheduled by a contractor via Hello! on 8/1/2006 at 10:00:45 AM. Contact: ###-####. ok anop
ELE06-02848 Electrical Rough-In8/2/20068/2/20068/2/2006 3:16:28 PMPPART
this is for a ceiling inspection, any questions please cal Steve Nuxoll; Phone #: ###-#### Internet Inspection Request from: Jeff Radford ok
ELE06-02817 Rough-In Permanent Service8/1/20068/2/20068/2/2006 2:17:10 PMPNR
Larry ###-####
ELE06-02817 Conference8/1/20068/2/20068/2/2006 2:16:53 PMPDONE
Larry ###-#### ok
ELE06-00895 Final8/2/20068/2/20068/2/2006 12:48:23 PMPFAIL
key code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson left job general mad ,calling me manes, corr. 110.26(F)(2) complete low voltage wiring by p/s so I can inspect for clearence
ELE06-00896 Final8/2/20068/2/20068/2/2006 12:46:28 PMPFAIL
key code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson left job general mad called me manes, corr. 110.26(F)(2) complete low voltage wiring so I can check for clearence at p/s
ELE06-01129 Final8/2/20068/2/20068/2/2006 12:44:00 PMPFAIL
key code ###-####; Phone #: ###-#### Internet Inspection Request from: Tracy Robertson left job general mad and calling me names corr. needs to remvove low voltage from below p/s 110.26 (F)(2)
ELE06-02116 Final8/1/20068/2/20068/2/2006 10:55:01 AMAPASS
need final inspection on new building. thank you. call chris @ ###-#### with any questions; Phone #: ###-#### Internet Inspection Request from: BRIAN KEITH
ok card signed needs fixture in closet instaled general called elctrical contr.
ELE06-00783 Electrical Rough-In8/1/20068/2/20068/2/2006 10:46:07 AMAPASS
laberta - call prior to insp for access(follow-up); Phone #: ###-#### Internet Inspection Request from: Barbara Buckley ok bathrm ok new tub shower ok it is listed
ELE06-02837 Electrical Rough-In8/1/20068/2/20068/2/2006 10:07:09 AMAPART
clyde - downstairs only for this insp; Phone #: ###-#### Internet Inspection Request from: Barbara Buckley 1st floor ok
ELE06-02049 Permanent Service8/1/20068/2/20068/2/2006 9:33:07 AMAPART
Equi-Potential Bonding Pool, Slide, Board Alt phone ###-#### 9414576; Phone #: ###-#### Internet Inspection Request from: Cathy Felin ok
ELE06-02827 Permanent Service8/2/20068/2/20068/2/2006 9:23:14 AMANR
SCOTT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy met contractor see added conference
ELE06-02827 Conference8/2/20068/2/20068/2/2006 9:22:35 AMADONE
SCOTT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy ok
ELE06-02827 Permanent Service8/1/20068/2/20068/2/2006 7:26:38 AMPCANC
SCOTT; Phone #: ###-#### Internet Inspection Request from: Sean DeLacy Inspection cancelled from web by: Sean DeLacy