BLD02-01532
| BLD-Aging Inspection | 8/2/2006 | 8/2/2006 | 8/8/2006 9:06:55 AM | | DEFR |
|
|
|
BLD03-01020
| BLD-Aging Inspection | 8/2/2006 | 8/2/2006 | 8/8/2006 9:04:53 AM | | DEFR |
|
|
|
FIR06-00337
| INSP-Sprinkler Rough-in | 8/1/2006 | 8/2/2006 | 8/3/2006 2:33:20 PM | A | PART |
|
|
Rough-in at the drop ceiling areas in the chemical lab are good for cover, final pending inspection for the remainder of relocated heads in the adjacent cleanroom.
|
FIR06-00258
| INSP-Final Inspection | 8/1/2006 | 8/2/2006 | 8/3/2006 12:56:05 PM | A | FAIL |
|
|
Notification device in the library is missing.
|
BLD05-02001
| FIRE-Final Inspection | 8/2/2006 | 8/2/2006 | 8/3/2006 11:23:08 AM | P | FAIL |
|
|
Fire dept. access lane marking does not meet requirements of current resubmitted approved plans, extend curb painting and hatched no parking stripes as discussed and indicated per plan.
|
BLD05-03139
| FIRE-Final Inspection | 8/2/2006 | 8/2/2006 | 8/3/2006 10:39:47 AM | P | PASS |
|
|
Life safety field inspection passed.
|
FIR05-00632
| INSP-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 4:50:11 PM | A | PASS |
|
|
Fire alarm work passed field inspection, updated map posted and incorrect PS descriptor changed while on site.
|
FIR06-00210
| INSP-Final Inspection | 8/1/2006 | 8/2/2006 | 8/2/2006 3:28:21 PM | A | PASS |
|
|
Final inspection passed permit finaled.
|
FIR05-00451
| FIR-Aging Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 1:39:41 PM | | DEFR |
|
|
|
FIR06-00355
| INSP-Sprinkler Rough-in | 8/1/2006 | 8/2/2006 | 8/2/2006 1:38:00 PM | P | CANC |
|
|
Notified contractor to final aging permits on the same building prior to request for inspeciton on additional new permits.
|
FIR06-00357
| INSP-Sprinkler Rough-in | 8/1/2006 | 8/2/2006 | 8/2/2006 1:36:26 PM | P | CANC |
|
|
Notified contractor to final aging permits on the same building prior to request for inspection on additional new permits.
|
FIR06-00322
| INSP-Sprinkler Rough-in | 8/1/2006 | 8/2/2006 | 8/2/2006 1:35:09 PM | P | CANC |
|
|
Notified contractor to final aging permits on the same building prior to request for inspections on additional new permits.
|
BLD06-02078
| FIRE-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 1:33:09 PM | P | PASS |
|
|
Final life safety inspection passed.
|
BLD06-00242
| FIRE-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 1:09:23 PM | P | PASS |
|
|
Inspection passed, no card available on site for signature.
|
FIR06-00494
| INSP-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 12:44:06 PM | P | FAIL |
|
|
HVAC duct detector incorrectly reports as alarm condition and is not identified correctly at remote station monitoring.
|
FIR06-00490
| INSP-Final Inspection | 8/2/2006 | 8/2/2006 | 8/2/2006 12:40:35 PM | A | PASS |
|
|
Fire sprinkler work passed field inspection, noted display cabinets blocking hose station to be relocated.
|
BLD06-00863
| FIRE-Final Inspection | 8/1/2006 | 8/2/2006 | 8/2/2006 12:10:39 PM | A | FAIL |
|
|
The project related fire alarm work failed inspection, also need to remove the keyed locking hardware at the door from office area.
|
BLD05-02453
| FIRE-Final Inspection | 8/1/2006 | 8/2/2006 | 8/2/2006 11:19:56 AM | A | PASS |
|
|
Required correction for the fire dept. access curb painting has been verified for completion, final inspection passed.
|
FIR06-00487
| INSP-Sprinkler Rough-in/Hydro | 8/1/2006 | 8/2/2006 | 8/2/2006 10:44:01 AM | A | PART |
|
|
Hydrostatic test for the new rack sprinklers at three areas is satisfactory, items on previous c/n have been verified for completion, added sprinklers at halo above the mountain are acceptable. Need to perform forward flow, test new tampers at the backflow, noted the ball drip at the FDC is leaking.
|
BLD06-02078
| FIRE-Final Inspection | 8/1/2006 | 8/2/2006 | 8/2/2006 10:00:28 AM | A | PART |
|
|
Items on previous correction notice have been completed, smoke evac system did not pass functional test.
|
FIR06-00547
| INSP-Final Inspection | 7/31/2006 | 8/2/2006 | 8/2/2006 9:57:25 AM | A | PASS |
|
|
Fire sprinkler passed final inspection.
|