Inspections for the day of: Thursday, August 2, 2007.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE07-02351 Electrical Rough-In8/2/20078/2/20078/2/2007 3:48:02 PMPFAIL
carol Phone #: ###-#### met owner, left corr notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members, 110.26(A) shall provide work space in front of sub-panel in garage
ELE07-02653 Permanent Service8/2/20078/2/20078/2/2007 3:26:41 PMPFAIL
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called left corr notice, nec 300.5 raceways shall be 18" deep to top conduit, 250.28 shall install main bonding jumper screw in shop panel, 408.4 shall provide circuit directory, 110.26(A) shall provide workspace in front of sub-panel in garage to check for isolated ground and neutral
ELE07-02688 Temporary Service8/2/20078/2/20078/2/2007 2:44:15 PMPCANC
Please call AJ Lehman with any questions. This is to inspect for a temp. power meter to be set Phone #: ###-#### Internet Inspection Request from: todd hall called, wrong type request, told to call for am with what want, put on correct address, label meter sockets
ELE07-01624 Electrical Rough-In8/2/20078/2/20078/2/2007 12:17:02 PMPPASS
Scheduled by a contractor via Hello! on 8/2/2007 at 8:45:31 AM. Contact: ###-####. ok to cover lot lighting east and south, note plans ltr
ELE07-02682 Final8/2/20078/2/20078/2/2007 11:48:24 AMPPASS
Rob ###-#### corrections made, ric ok, ok to final
ELE07-00392 Final8/2/20078/2/20078/2/2007 11:26:28 AMPPASS
Rod ###-#### corr made, ok to final
ELE07-02691 Electrical Rough-In8/1/20078/2/20078/2/2007 10:47:31 AMAPASS
Jarrod Clymer Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok
ELE07-02547 Electrical Rough-In8/2/20078/2/20078/2/2007 10:22:08 AMAPASS
Contact is Eric. Ceiling inspection in Deli Dept. Phone #: ###-#### Internet Inspection Request from: David Bonner deli ceiling only ok to cover
ELE07-02285 Electrical Rough-In8/1/20078/2/20078/2/2007 9:47:30 AMACANC
Phone #: ###-#### Internet Inspection Request from: Steve Craig met contr, asked to cancel this inspection request
ELE07-02286 Electrical Rough-In8/1/20078/2/20078/2/2007 9:19:44 AMAPASS
Phone #: ###-#### Internet Inspection Request from: Steve Craig met contr, ceiling only ok to cover, he will add suite number to permit
ELE07-02473 Electrical Rough-In8/2/20078/2/20078/2/2007 8:49:21 AMAFAIL
trench inspection for demolished portion of parking lot Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left corr notice, 300.5 u/g conduit shall be 24" deep to top of raceway at entry point off Ustick
ELE07-00889 Electrical Rough-In8/1/20078/2/20078/2/2007 8:17:17 AMAPASS
call Randy for morning inspection of site pole lighting.Thanks Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called, u/g for parking lot lights ok to cover
ELE07-02466 Electrical Rough-In8/1/20078/2/20078/2/2007 7:51:51 AMAPASS
james Phone #: ###-#### ok to cover floor heat only, entry, and large room