ELE07-02351
| Electrical Rough-In | 8/2/2007 | 8/2/2007 | 8/2/2007 3:48:02 PM | P | FAIL |
|
|
carol Phone #: ###-#### met owner, left corr notice, nec 300.4(D) edge of nm cable shall be 1 1/4" from edge of framing members, 110.26(A) shall provide work space in front of sub-panel in garage
|
ELE07-02653
| Permanent Service | 8/2/2007 | 8/2/2007 | 8/2/2007 3:26:41 PM | P | FAIL |
|
|
permanent service and underground Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called left corr notice, nec 300.5 raceways shall be 18" deep to top conduit, 250.28 shall install main bonding jumper screw in shop panel, 408.4 shall provide circuit directory, 110.26(A) shall provide workspace in front of sub-panel in garage to check for isolated ground and neutral
|
ELE07-02688
| Temporary Service | 8/2/2007 | 8/2/2007 | 8/2/2007 2:44:15 PM | P | CANC |
|
|
Please call AJ Lehman with any questions. This is to inspect for a temp. power meter to be set Phone #: ###-#### Internet Inspection Request from: todd hall called, wrong type request, told to call for am with what want, put on correct address, label meter sockets
|
ELE07-01624
| Electrical Rough-In | 8/2/2007 | 8/2/2007 | 8/2/2007 12:17:02 PM | P | PASS |
|
|
Scheduled by a contractor via Hello! on 8/2/2007 at 8:45:31 AM. Contact: ###-####. ok to cover lot lighting east and south, note plans ltr
|
ELE07-02682
| Final | 8/2/2007 | 8/2/2007 | 8/2/2007 11:48:24 AM | P | PASS |
|
|
Rob ###-#### corrections made, ric ok, ok to final
|
ELE07-00392
| Final | 8/2/2007 | 8/2/2007 | 8/2/2007 11:26:28 AM | P | PASS |
|
|
Rod ###-#### corr made, ok to final
|
ELE07-02691
| Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 10:47:31 AM | A | PASS |
|
|
Jarrod Clymer Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer ric ok
|
ELE07-02547
| Electrical Rough-In | 8/2/2007 | 8/2/2007 | 8/2/2007 10:22:08 AM | A | PASS |
|
|
Contact is Eric. Ceiling inspection in Deli Dept. Phone #: ###-#### Internet Inspection Request from: David Bonner deli ceiling only ok to cover
|
ELE07-02285
| Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 9:47:30 AM | A | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig met contr, asked to cancel this inspection request
|
ELE07-02286
| Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 9:19:44 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Steve Craig met contr, ceiling only ok to cover, he will add suite number to permit
|
ELE07-02473
| Electrical Rough-In | 8/2/2007 | 8/2/2007 | 8/2/2007 8:49:21 AM | A | FAIL |
|
|
trench inspection for demolished portion of parking lot Phone #: ###-#### Internet Inspection Request from: Jarrod Clymer called, left corr notice, 300.5 u/g conduit shall be 24" deep to top of raceway at entry point off Ustick
|
ELE07-00889
| Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 8:17:17 AM | A | PASS |
|
|
call Randy for morning inspection of site pole lighting.Thanks Phone #: ###-#### Internet Inspection Request from: Loren Ramsey called, u/g for parking lot lights ok to cover
|
ELE07-02466
| Electrical Rough-In | 8/1/2007 | 8/2/2007 | 8/2/2007 7:51:51 AM | A | PASS |
|
|
james Phone #: ###-#### ok to cover floor heat only, entry, and large room
|