Inspections for the day of: Friday, August 2, 2013.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR13-00307 INSP-Final Inspection7/31/20138/2/20138/6/2013 3:37:23 PMADEFR
Devices installed per plans and tested ok. The issue is the two new visual devices are the only visual devices in a large open office space that currently only has audible signals. Per the fire alarm contractor an "upgrade agreement" exists for this building. I have deferred approval to Scott Arellano/Fire Dept.
FIR06-00015 INSP-Final Inspection8/2/20138/2/20138/2/2013 3:32:17 PMPPASS
Permit finaled
FIR13-00305 INSP-Sprinkler Rough-in8/2/20138/2/20138/2/2013 3:28:20 PMPPART
rough-in passed. As-builts are needed prior to a final sign off that show theactual pipe routing. Piping can not be covered until a tenting inspection has been performed. Also the underground supply is a combined service with the domestic which, as noted on the city approved plans/notes, is not United Water approved.
BLD13-01603 FIRE-Final Inspection8/1/20138/2/20138/2/2013 1:29:28 PMAPASS
Life safety passed
FIR13-00304 INSP-Final Inspection8/2/20138/2/20138/2/2013 1:28:52 PMPPASS
Permit finaled
BLD13-02030 FIRE-Final Inspection8/1/20138/2/20138/2/2013 11:14:36 AMAPASS
Life safety passed.
FIR13-00256 INSP-Final Inspection8/1/20138/2/20138/2/2013 11:12:11 AMAPASS
Permit finaled
FIR13-00314 INSP-Sprinkler Rough-in8/1/20138/2/20138/2/2013 10:18:04 AMAPASS
The supply piping that was installed as 1" has been correct to match the required 1 1/4". The piping in the restroom walls can now be covered.
FIR12-00199 INSP-Final Inspection7/31/20138/2/20138/2/2013 9:36:14 AMAPASS
Permit finaled
FIR13-00126 INSP-Alarm Testing8/1/20138/2/20138/2/2013 7:13:01 AMADONE
Alarm testing for Prep/Rec 103/104 and the west entry passed.