Inspections for the day of: Tuesday, August 2, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE13-02322 ELE-Aging Inspection8/2/20168/2/20168/5/2016 6:46:45 AM CANC
ELE11-00142 ELE-Aging Inspection8/2/20168/2/20168/5/2016 6:46:20 AM CANC
ELE16-01838 Electrical Rough-In8/1/20168/2/20168/2/2016 3:36:46 PMPPASS
ceiling inspection Level 8 stack 4, call John. Phone #: ###-#### Inspection requested via web by Brandon Robinson
Level 8 stack 3 south and 4 ceiling rough in ok cover.
ELE16-00089 Conference8/1/20168/2/20168/2/2016 2:53:36 PMADONE
Call Rafael to discuss outlets in ceiling area of ballroom. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Discussed location of receptacle outlets above a "grid cloud". Flexible cords are not to be installed above grid in any application as per NEC 400.8 uses not permitted. Receptacle outlets shown for temporary equipment for events shall be mounted in or below grid level.
ELE15-03901 Conference8/2/20168/2/20168/2/2016 11:32:13 AMPDONE
Sign TCO sheets for 6th and 7th floor that ESI now has set up in a binder as per Dave Hannah''s request. Phone #: ###-#### Inspection requested via web by Rafael Castillo
Signed off on floors 6 and 7 in new book provided
ELE16-00303 Electrical Rough-In8/1/20168/2/20168/2/2016 11:30:51 AMAPART
TCO inspection.
Contact is Toby Groves ###-#### Phone #: ###-#### Inspection requested via web by Toby Groves
Floor 2- complete central stair lighting. Framing at main floor entrance, sconce omitted, flourescent under landings not installed may be omitted. Covers missing for card readers on several walls. Cover gutter i electrical room.
3rd floor- Server room fire suppression, HVAC, rack yet to complete. Door shall be lockable and missing window. Card reader boxes at several locations not covered. Room 368 conference table power supply not compatible with floor box provided. location different. Armored cable whip provided and receptacle installed in floor.
ELE15-02641 Electrical Rough-In8/1/20168/2/20168/2/2016 9:27:03 AMAPASS
3rd ; 4th Floor Corridor drops Phone #: ###-#### Inspection requested via web by Kerri Hamilton
Floor 3, 4, 5, corridor drop hardlids rough in ok cover
ELE16-02484 Electrical Rough-In8/1/20168/2/20168/2/2016 9:07:35 AMAPASS
Roberts. Cover Phone #: ###-#### Inspection requested via web by Sean DeLacy
Wall rough in ok cover
ELE15-02740 Electrical Rough-In8/1/20168/2/20168/2/2016 8:44:54 AMAPASS
Seth Phone #: ###-####
Main lobby and breakfast area grid rough in ok cover
ELE15-03901 Electrical Rough-In8/2/20168/2/20168/2/2016 7:53:21 AMPCANC
Call Rafael for pre-walk final of 8th floor. Phone #: ###-#### >> Inspection requested via web by Rafael Castillo Inspection cancelled from web by: Rafael Castillo
ELE15-03901 Electrical Rough-In8/1/20168/2/20168/2/2016 7:51:03 AMACANC
Pre-walk 8th floor to prepare for final inspection of the floor. Review and sign TCO sign-off sheet for 6th anf 7th floors as per Dave Hannah''s request. Call Rafael for inspection. Phone #: ###-#### >> Inspection requested via web by Rafael Castillo Inspection cancelled from web by: Rafael Castillo