Inspections for the day of: Tuesday, August 2, 2016.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJim Page
TitleFIRE INSPECTOR
Phone #208-914-5431
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR16-00432 INSP-Final Inspection8/2/20168/2/20168/2/2016 7:31:31 PMPFAIL
Final fire alarm inspection performed for new fire alarm panel and associated devices. All audio visual devices tested, tampers and flow from fire sprinkler system reported to fire panel. Tested pull station as well as smoke by FACP. All devices test satisfactorily but did not report out to monitoring service. Alarm signals need to be verfied by monitoring service before FIR permit can be finaled.
BLD16-02567 FIRE-Final Inspection8/2/20168/2/20168/2/2016 3:42:10 PMPPASS
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
FIR16-00265 INSP-Sprinkler Rough-in8/1/20168/2/20168/2/2016 3:05:24 PMAPART
Rough to cover inspection complete for heads in soffit by main north stairs, need to verify proper installation for dry pendants in soffit area east of the main stairs.
BLD16-02716 FIRE-Final Inspection8/2/20168/2/20168/2/2016 2:57:58 PMPPASS
No fire sprinkler modifications, one fire sprinkler missing escutcheon that will be installed by property manager, no fire alarm modifications, fire extinguisher is mounted in common area with current inspection tag. Final life fire safety inspection passed/complete.
FIR16-00127 INSP-Final Inspection8/1/20168/2/20168/2/2016 12:58:57 PMAPART
Fire alarm inspection complete for levels 2 and 3.
FIR16-00227 INSP-Sprinkler Rough-in/Hydro8/1/20168/2/20168/2/2016 12:57:30 PMAPART
200 psi hydrostatic test complete, 24 hour air test started at 12:00 pm @ 40psi
FIR16-00363 INSP-Final Inspection8/1/20168/2/20168/2/2016 12:56:35 PMAPASS
Final fire alarm inspection passed/complete.
FIR16-00057 INSP-Final Inspection8/2/20168/2/20168/2/2016 10:13:03 AMAPASS
Final fire sprinkler inspection for level 2 passed/complete
FIR16-00146 INSP-Sprinkler Rough-in8/1/20168/2/20168/2/2016 9:41:52 AMPPASS
Rough to cover inspection for overhead fire sprinkler piping on level 8 complete, overhead fire sprinkler piping on level 8 approved for cover.
FIR15-00705 INSP-Sprinkler Rough-in/Hydro8/1/20168/2/20168/2/2016 9:40:54 AMPFAIL
Rough to cover inspection for overhead fire sprinkler piping on level 4 annex partially complete. Sprinkler heads missing in soffit by center stairs, head needs to be added by kitchen hood locedt in the southwest area, head is currently overspaced. Heads in soffit on southeast side spaced to far from edge of soffit, heads need to be relocated. No heads under south stairs from 5 to 4, need to verify head coverage for these stairs. Items need to be corrected before cover is approved.
FIR15-00561 INSP-Sprinkler Rough-in8/1/20168/2/20168/2/2016 8:37:21 AMAPASS
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 approved for cover. Rough to cover inspection complete for overhead fire sprinkler piping located above the hardlids on level 1, overhead fire sprinkler piping located above the hardlids on level 1 approved for cover