FIR16-00432
| INSP-Final Inspection | 8/2/2016 | 8/2/2016 | 8/2/2016 7:31:31 PM | P | FAIL |
|
|
Final fire alarm inspection performed for new fire alarm panel and associated devices. All audio visual devices tested, tampers and flow from fire sprinkler system reported to fire panel. Tested pull station as well as smoke by FACP. All devices test satisfactorily but did not report out to monitoring service. Alarm signals need to be verfied by monitoring service before FIR permit can be finaled.
|
BLD16-02567
| FIRE-Final Inspection | 8/2/2016 | 8/2/2016 | 8/2/2016 3:42:10 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR16-00265
| INSP-Sprinkler Rough-in | 8/1/2016 | 8/2/2016 | 8/2/2016 3:05:24 PM | A | PART |
|
|
Rough to cover inspection complete for heads in soffit by main north stairs, need to verify proper installation for dry pendants in soffit area east of the main stairs.
|
BLD16-02716
| FIRE-Final Inspection | 8/2/2016 | 8/2/2016 | 8/2/2016 2:57:58 PM | P | PASS |
|
|
No fire sprinkler modifications, one fire sprinkler missing escutcheon that will be installed by property manager, no fire alarm modifications, fire extinguisher is mounted in common area with current inspection tag. Final life fire safety inspection passed/complete.
|
FIR16-00127
| INSP-Final Inspection | 8/1/2016 | 8/2/2016 | 8/2/2016 12:58:57 PM | A | PART |
|
|
Fire alarm inspection complete for levels 2 and 3.
|
FIR16-00227
| INSP-Sprinkler Rough-in/Hydro | 8/1/2016 | 8/2/2016 | 8/2/2016 12:57:30 PM | A | PART |
|
|
200 psi hydrostatic test complete, 24 hour air test started at 12:00 pm @ 40psi
|
FIR16-00363
| INSP-Final Inspection | 8/1/2016 | 8/2/2016 | 8/2/2016 12:56:35 PM | A | PASS |
|
|
Final fire alarm inspection passed/complete.
|
FIR16-00057
| INSP-Final Inspection | 8/2/2016 | 8/2/2016 | 8/2/2016 10:13:03 AM | A | PASS |
|
|
Final fire sprinkler inspection for level 2 passed/complete
|
FIR16-00146
| INSP-Sprinkler Rough-in | 8/1/2016 | 8/2/2016 | 8/2/2016 9:41:52 AM | P | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 8 complete, overhead fire sprinkler piping on level 8 approved for cover.
|
FIR15-00705
| INSP-Sprinkler Rough-in/Hydro | 8/1/2016 | 8/2/2016 | 8/2/2016 9:40:54 AM | P | FAIL |
|
|
Rough to cover inspection for overhead fire sprinkler piping on level 4 annex partially complete. Sprinkler heads missing in soffit by center stairs, head needs to be added by kitchen hood locedt in the southwest area, head is currently overspaced. Heads in soffit on southeast side spaced to far from edge of soffit, heads need to be relocated. No heads under south stairs from 5 to 4, need to verify head coverage for these stairs. Items need to be corrected before cover is approved.
|
FIR15-00561
| INSP-Sprinkler Rough-in | 8/1/2016 | 8/2/2016 | 8/2/2016 8:37:21 AM | A | PASS |
|
|
Rough to cover inspection for overhead fire sprinkler piping located on level 4 complete, overhead fire sprinkler piping located on level 4 approved for cover. Rough to cover inspection complete for overhead fire sprinkler piping located above the hardlids on level 1, overhead fire sprinkler piping located above the hardlids on level 1 approved for cover
|