BLD17-00822
| FIRE-Final Inspection | 8/2/2017 | 8/2/2017 | 8/2/2017 1:37:52 PM | P | PASS |
|
|
No fire sprinklers, no fire alarms, fire extinguishers are in place with current inspection tags. Final life fire safety inspection passed/complete.
|
FIR17-00206
| INSP-Sprinkler Rough-in/Hydro | 8/1/2017 | 8/2/2017 | 8/2/2017 1:36:37 PM | P | PASS |
|
|
Underground hydrostatic test complete
|
BLD15-01124
| FIRE-Final Inspection | 8/2/2017 | 8/2/2017 | 8/2/2017 12:44:31 PM | P | PASS |
|
|
Fire sprinkler inspection is complete, fire alarm inspection is complete, fire extinguishers are in place with current inspection tags, knox box is mounted next to fire sprinkler riser room, signage for fire sprinkler riser room will be installed afetr door is painted. Final life fire safety inspection passed/complete.
|
FIR17-00174
| INSP-Final Inspection | 8/1/2017 | 8/2/2017 | 8/2/2017 12:38:52 PM | A | PASS |
|
|
Final fire alarm inspection passed/complete
|
BLD16-00912
| FIRE-Final Inspection | 8/1/2017 | 8/2/2017 | 8/2/2017 12:01:56 PM | P | PASS |
|
|
Permit was re-assigned to a "vanilla" tenant inprovement. Prior to future occupants the door hardware on the north doors will need to be changed to panic hardware, designated exits on the south and east side will need to be changed to single action door hardware with thumbturn deadbolts removed. There is an issued FIR permit for the commercial hood fire suppression system (FIR17-00079) but no inspection can be performed due to no cooking equipment being installed, prior to next tenant the issued FIR permit will need to be inspected and completed. No fire extinguishers installed at time of inspection, fire extinguishers are not required under a vanilla TI. No occupancy allowed under this life fire safety inspection, life fire safety inspection complete for vanilla finish.
|
BLD17-00445
| FIRE-Final Inspection | 8/1/2017 | 8/2/2017 | 8/2/2017 10:43:39 AM | P | CANC |
|
|
Duplicate inspection request, this inspection request for fire life safety is cancelled
|
BLD17-00445
| FIRE-Final Inspection | 8/1/2017 | 8/2/2017 | 8/2/2017 10:42:49 AM | A | FAIL |
|
|
1. Escutcheon in southwest cooler missing on dry pendant. 2. Exit discharge landing light on northwest exit did not illuminate when test button was pushed. 3. Emergency lighting in seating area and west hall not operational. 4. West emergency exit does not have discharge landing egress lighting installed, discharge landing emergency egress lighting needs to be installed. 5. Exit sign needs to be installed in south brewing area above south door leading to designated exterior ext in storage area. 6. Exit sign/emergency lighting needs to be installed in south storage area to include exit discharge landing illumination. 7. No fire extinguishers installed at time of inspection.
|
FIR16-00760
| INSP-Final Inspection | 8/1/2017 | 8/2/2017 | 8/2/2017 9:19:41 AM | A | PASS |
|
|
Final fire sprinkler inspection passed/complete
|
FIR17-00144
| INSP-Supply line flush | 8/1/2017 | 8/2/2017 | 8/2/2017 9:19:09 AM | A | DONE |
|
|
Underground supply line flush complete
|
FIR17-00144
| INSP-Supply line flush | 8/1/2017 | 8/2/2017 | 8/1/2017 4:02:57 PM | A | CANC |
|
|
Trying to coordinate a time with Stacy at Suez. Call Jake in AM to discuss. Phone #: ###-#### >> Inspection requested via web by Anthony Minichiello Inspection cancelled from web by: Anthony Minichiello
|