BLD18-00434
| FIRE-Conference | 8/2/2018 | 8/2/2018 | 8/2/2018 2:34:14 PM | P | DONE |
|
|
I spoke to both Stan and Zac about the need to meet with the fire alarm plan reviewer and verify permit requirements and the possible need to connect the duct smoke detectors to the existing fire alarm system.
|
FIR17-00683
| INSP-Final Inspection | 8/1/2018 | 8/2/2018 | 8/2/2018 2:01:45 PM | A | CANC |
|
|
As-builts have not been provided to plan review yet.
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
FIR18-00571
| INSP-Sprinkler Rough-in/Hydro | 8/1/2018 | 8/2/2018 | 8/2/2018 1:45:25 PM | A | PASS |
|
|
See the city approved plans for location where rough-in passed and piping can be covered.
Mike Phone #: ###-####
|
BLD18-02399
| FIRE-Final Inspection | 8/1/2018 | 8/2/2018 | 8/2/2018 1:02:54 PM | A | PASS |
|
|
life safety passed
call 10 mins ahead- Duane Phone #: ###-####
|
BLD18-00561
| FIRE-Final Inspection | 7/31/2018 | 8/2/2018 | 8/2/2018 11:16:14 AM | A | PASS |
|
|
Life safety passed
Jim Phone #: ###-####
|
NAF18-00066
| INSP-Final | 8/2/2018 | 8/2/2018 | 8/2/2018 10:41:56 AM | A | CANC |
|
|
Not ready for inspection. WIll need to reschedule
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
|
NAF18-00064
| INSP-Final | 8/2/2018 | 8/2/2018 | 8/2/2018 10:41:17 AM | A | CANC |
|
|
Not ready for inspection. Will need to reschedule
Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
|
FIR18-00446
| INSP-Final Inspection | 8/1/2018 | 8/2/2018 | 8/2/2018 9:59:52 AM | A | PASS |
|
|
Permit finaled
Phone #: ###-#### Inspection requested via web by Gary Gambino
|
NAF18-00013
| INSP-Final | 8/2/2018 | 8/2/2018 | 8/2/2018 9:30:55 AM | A | FAIL |
|
|
Need as-builts, need to test elevator, need elevator doors on first and second floors to latch, need strobe raised in third floor restroom, need speaker added in third floor mech room, need correct size batteries in facp.
Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
NAF17-00091
| INSP-Final | 8/1/2018 | 8/2/2018 | 8/2/2018 9:03:02 AM | A | PASS |
|
|
Permit finaled
|
NAF18-00060
| INSP-Final | 8/1/2018 | 8/2/2018 | 8/2/2018 9:00:47 AM | A | FAIL |
|
|
See the city approved plans for corrections needed which include strobe coverage issues in the Gym due to STI covers on the strobes, overspaced strobes and areas where strobes are needed. As-builts will be required prior to a final sign off.
As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
|
BLD18-00771
| FIRE-Final Inspection | 8/1/2018 | 8/2/2018 | 8/2/2018 12:00:00 AM | A | CANC |
|
|
cancel per Justin Phone #: ###-####
|