Inspections for the day of: Thursday, August 2, 2018.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD18-00434 FIRE-Conference8/2/20188/2/20188/2/2018 2:34:14 PMPDONE
I spoke to both Stan and Zac about the need to meet with the fire alarm plan reviewer and verify permit requirements and the possible need to connect the duct smoke detectors to the existing fire alarm system.
FIR17-00683 INSP-Final Inspection8/1/20188/2/20188/2/2018 2:01:45 PMACANC
As-builts have not been provided to plan review yet.

Phone #: ###-#### Inspection requested via web by Gary Gambino
FIR18-00571 INSP-Sprinkler Rough-in/Hydro8/1/20188/2/20188/2/2018 1:45:25 PMAPASS
See the city approved plans for location where rough-in passed and piping can be covered.

Mike Phone #: ###-####
BLD18-02399 FIRE-Final Inspection8/1/20188/2/20188/2/2018 1:02:54 PMAPASS
life safety passed


call 10 mins ahead- Duane Phone #: ###-####
BLD18-00561 FIRE-Final Inspection7/31/20188/2/20188/2/2018 11:16:14 AMAPASS
Life safety passed


Jim Phone #: ###-####
NAF18-00066 INSP-Final8/2/20188/2/20188/2/2018 10:41:56 AMACANC
Not ready for inspection. WIll need to reschedule


Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
NAF18-00064 INSP-Final8/2/20188/2/20188/2/2018 10:41:17 AMACANC
Not ready for inspection. Will need to reschedule

Call prior to going Phone #: 2088693329 >> Inspection requested via mobile web by Mike
FIR18-00446 INSP-Final Inspection8/1/20188/2/20188/2/2018 9:59:52 AMAPASS
Permit finaled

Phone #: ###-#### Inspection requested via web by Gary Gambino
NAF18-00013 INSP-Final8/2/20188/2/20188/2/2018 9:30:55 AMAFAIL
Need as-builts, need to test elevator, need elevator doors on first and second floors to latch, need strobe raised in third floor restroom, need speaker added in third floor mech room, need correct size batteries in facp.

Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
NAF17-00091 INSP-Final8/1/20188/2/20188/2/2018 9:03:02 AMAPASS
Permit finaled
NAF18-00060 INSP-Final8/1/20188/2/20188/2/2018 9:00:47 AMAFAIL
See the city approved plans for corrections needed which include strobe coverage issues in the Gym due to STI covers on the strobes, overspaced strobes and areas where strobes are needed. As-builts will be required prior to a final sign off.


As early as possible Phone #: 2088301311 >> Inspection requested via mobile web by Nathan Price
BLD18-00771 FIRE-Final Inspection8/1/20188/2/20188/2/2018 12:00:00 AMACANC
cancel per Justin Phone #: ###-####