Inspections for the day of: Friday, August 2, 2019.
Number of inspections: 10
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRock A. Hudson
TitleELE-INSPECTOR
Phone #794-6794
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE19-01138 Final7/31/20198/2/20198/2/2019 2:33:01 PMPPASS
Phone #: ###-#### Inspection requested via web by Steve VanWinkle Final ok
ELE19-01138 Electrical Rough-In8/2/20198/2/20198/2/2019 2:01:16 PMPPASS
Phone #: ###-#### Inspection requested via web by Steve VanWinkle
Listing confirmed rough in ok
ELE19-01961 Final8/2/20198/2/20198/2/2019 2:00:28 PMPPASS
Final Phone #: ###-#### Inspection requested via web by Casey Fouts Final ok
ELE19-02635 Final8/2/20198/2/20198/2/2019 1:37:43 PMPPASS
Phone #: ###-#### Inspection requested via web by Jim Noll Final ok
ELE19-01087 Final7/31/20198/2/20198/2/2019 11:47:04 AMAPASS
Phone #: ###-#### Inspection requested via web by Steve VanWinkle Final ok
ELE19-01087 Electrical Rough-In8/2/20198/2/20198/2/2019 11:17:12 AMPPASS
Phone #: ###-#### Inspection requested via web by Steve VanWinkle
Listing confirmed on all. Rough in ok cover.
ELE19-02196 Final8/1/20198/2/20198/2/2019 11:15:58 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-02195 Final8/1/20198/2/20198/2/2019 10:51:55 AMAPASS
Phone #: ###-#### Inspection requested via web by Darryn Coburn Final ok
ELE19-00947 Electrical Rough-In8/1/20198/2/20198/2/2019 10:17:19 AMAPASS
Andy-underground Phone #: ###-####
All conduits in this area covered priot to inspeciton.
BCC 4-05-23- It shall be unlawful for any person to cover up or in any way conceal any electrical wiring, cables, conduits, or other equipment until the same has been inspected and approved by an electrical inspector.
Area (B) has minimal conduit runs and is to be under concrete, all future installation shall be inspected prior to cover.
Area (B) underground rough in ok cover.
ELE19-02635 Final8/2/20198/2/20198/2/2019 9:31:24 AMAFAIL
Tenant space on the corner of 8th and Idaho on the 1st floor. Phone #: ###-#### Inspection requested via web by Jim Noll
314.25- All boxes shall have covers. Open swich box in work area, device covers missing thru out, wet floor glue in work area, no access to new receptacles.