MEC19-03100
| Rough-in | 8/2/2019 | 8/2/2019 | 8/2/2019 4:04:41 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Brian Preece- fp r/i ok
|
MEC19-03122
| Final | 7/30/2019 | 8/2/2019 | 8/2/2019 3:37:13 PM | P | PASS |
|
|
Phone #: ###-#### Inspection requested via web by Mary LaFayette- a/c coil co ok
|
MEC19-03390
| Rough-in | 8/2/2019 | 8/2/2019 | 8/2/2019 3:13:38 PM | P | PASS |
|
|
Add p test Phone #: ###-#### Inspection requested via web by Joe Taylor- r/i ok
|
MEC19-03390
| Pressure Test | 8/2/2019 | 8/2/2019 | 8/2/2019 3:13:19 PM | P | PASS |
|
|
Add rough in Phone #: ###-#### Inspection requested via web by Joe Taylor- 20lb gas pass tagged meter location
|
MEC19-03359
| Final | 8/1/2019 | 8/2/2019 | 8/2/2019 2:38:02 PM | P | PASS |
|
|
Please Call Rob on your way - ###-#### Phone #: ###-#### Inspection requested via web by Arielle Hendricks- mini split final ok
|
MEC19-03155
| Final | 7/29/2019 | 8/2/2019 | 8/2/2019 1:38:15 PM | P | PASS |
|
|
Inspection requested via web by Denise Colin- furnace a/c coil co ok
|
MEC19-00256
| Final | 8/2/2019 | 8/2/2019 | 8/2/2019 1:05:27 PM | P | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- final ok
|
MEC19-03232
| Rough-in | 8/2/2019 | 8/2/2019 | 8/2/2019 12:31:28 PM | P | PASS |
|
|
GARI ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fp r/i ok
|
MEC19-03367
| Pressure Test | 8/1/2019 | 8/2/2019 | 8/2/2019 11:08:17 AM | A | FAIL |
|
|
Please call Tony Bowe when headed to perform this inspection. Phone #: ###-#### Inspection requested via web by Tobi Wilson- gauge at 34psi on 100lb gauge- not sure if this is 2# system or low pressure- low pressure would require max 30lb gauge at over 20psi- do not backfill
|
MEC19-03321
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 10:38:05 AM | A | PASS |
|
|
VINNIE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fp r/i ok
|
MEC19-03272
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 10:34:03 AM | A | PASS |
|
|
VINNIE ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza- fp r/i ok
|
MEC19-03337
| Final | 7/30/2019 | 8/2/2019 | 8/2/2019 9:56:21 AM | A | CANC |
|
|
Inspection requested via web by Margie Rowe- inspection was finaled on 7-31-19
|
MEC19-03345
| Final | 8/1/2019 | 8/2/2019 | 8/2/2019 9:36:13 AM | A | PASS |
|
|
call james for contact Phone #: ###-#### Inspection requested via web by Jeremy lehosit- furnace a/c coil co ok- 5lb flue test pass
|
MEC19-02753
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 9:17:08 AM | P | PASS |
|
|
field super; Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- R/I ok
|
MEC19-02753
| Pressure Test | 8/1/2019 | 8/2/2019 | 8/2/2019 9:16:50 AM | P | PASS |
|
|
field super; Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- 20lb gas pass tagged meter location- 5lb flue pass
|
MEC19-02754
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 9:16:21 AM | P | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- R/I ok
|
MEC19-02754
| Pressure Test | 8/1/2019 | 8/2/2019 | 8/2/2019 9:16:06 AM | P | PASS |
|
|
Field super: Daryl Thomas Phone #: ###-#### Inspection requested via web by Lisa Whitney- 20lb gas pass tagged meter location- 5lb flue pass
|
MEC19-03329
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 9:02:22 AM | A | PASS |
|
|
RON ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
|
MEC19-03328
| Rough-in | 8/1/2019 | 8/2/2019 | 8/2/2019 9:02:09 AM | A | PASS |
|
|
RON ###-#### Phone #: ###-#### Inspection requested via web by Mike Almanza
|
MEC19-02194
| Final | 7/30/2019 | 8/2/2019 | 8/2/2019 8:32:02 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need duct blast test completed- need to seal lineset penetration at a/c location
|
MEC19-02193
| Final | 7/30/2019 | 8/2/2019 | 8/2/2019 8:31:19 AM | A | FAIL |
|
|
code 2468 Phone #: ###-#### Inspection requested via web by Randy Hart- need duct blast test completed
|
MEC18-05980
| Mec-Aging Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 8:06:40 AM | | FAIL |
|
|
contractor needs to schedule inspection- permit will expire next aging if no activity
|
MEC18-04340
| Mec-Aging Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 8:06:09 AM | | CANC |
|
|
WIP
|
MEC18-04519
| Mec-Aging Inspection | 8/2/2019 | 8/2/2019 | 8/2/2019 8:05:58 AM | | CANC |
|
|
|
MEC18-04519
| DOC - Permit Expired | 8/2/2019 | 8/2/2019 | 8/2/2019 8:05:51 AM | A | PASS |
|
|
no activity
|
MEC19-03367
| Pressure Test | 8/1/2019 | 8/2/2019 | 8/1/2019 1:59:59 PM | A | CANC |
|
|
Please call Tony Bowe @ ###-#### when you are headed to perform this inspection, if you could please schedule the inspection for mid to late morning that would be great. Phone #: ###-#### >> Inspection requested via web by Tobi Wilson Inspection cancelled from web by: Tobi Wilson
|