Inspections for the day of: Tuesday, August 20, 2002.
Number of inspections: 15
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE02-02442 Electrical Rough-In8/19/20028/20/20028/20/2002 12:00:00 AMAFAIL
###-#### 210.52(A) needs recept 2ft wall in new family rm, 250.148 grd outside light boxes, needs to check with structral on smoke detector locations? 8/20/2002 5:26:41 PM
ELE02-02523 Final8/19/20028/20/20028/20/2002 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 08/19/2002 at 15:48:55. Contact: ###-####. ok 8/20/2002 10:59:56 AM
ELE02-02583 Electrical Rough-In8/19/20028/20/20028/20/2002 12:00:00 AMAFAIL
GROUNDING ###-#### JOE cor. posted called 608.10 depht of pvc shall be 18 inches, also covered before inspection 8/20/2002 12:50:06 PM
ELE02-02165 Electrical Rough-In8/20/20028/20/20028/20/2002 12:00:00 AMAPART
Scheduled by a contractor via Hello! on 08/20/2002 at 07:11:39. Contact: ###-####. walls 8/20/2002 11:52:18 AM
ELE02-02559 Electrical Rough-In8/19/20028/20/20028/20/2002 12:00:00 AMAPASS
DAN; Phone #: ###-#### both baths ok 8/20/2002 3:24:13 PM
ELE02-02580 Electrical Rough-In8/20/20028/20/20028/20/2002 12:00:00 AMAPART
r/i and bond for inground spa ok 8/21/2002 10:54:10 AM
ELE02-02466 Electrical Rough-In8/19/20028/20/20028/20/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 08/19/2002 at 13:06:24. Contact: ###-####. u/g ok 8/20/2002 2:36:42 PM
ELE02-02367 Electrical Rough-In8/19/20028/20/20028/20/2002 12:00:00 AMPPART
###-#### john ceiling 8/20/2002 11:52:34 AM
ELE02-00325 Final8/19/20028/20/20028/20/2002 12:00:00 AMPPASS
CALL FIRST ###-#### KIM; Phone #: ###-####ok 8/19/2002 3:36:31 PM
ELE02-02580 Final8/20/20028/20/20028/20/2002 12:00:00 AMPNH
Scheduled by a contractor via Hello! on 08/20/2002 at 08:15:01. Contact: ###-####. called notice posted will do AM 08/21/02 8/20/2002 6:48:00 PM
ELE02-02582 Permanent Service8/20/20028/20/20028/20/2002 12:00:00 AMPFAIL
###-#### cor. posted called 250.28 bond screw,250.52,or104 grd or bond water system, 250.90 bond nipple between meter and p/s disconnect, 250 53(D)(2) 2 grd rods 230.28 strap mast, 110.26 make sure panel has clearence and dedicated space 8/20/2002 3:48:19 PM
ELE02-01877 Electrical Rough-In8/20/20028/20/20028/20/2002 12:00:00 AMPPART
Scheduled by a contractor via Hello! on 08/20/2002 at 08:47:57. Contact: ###-####. u/g for lights and electrode 8/20/2002 12:15:20 PM
ELE02-02528 Rough-In Permanent Service8/20/20028/20/20028/20/2002 12:00:00 AMPFAIL
Scheduled by a contractor via Hello! on 08/20/2002 at 10:42:35. Contact: ###-####. called contractor said it is duplex prints say different called J Storey he will check on it need to meet with contractor 8/20/2002 6:05:32 PM
ELE02-02596 Final8/20/20028/20/20028/20/2002 12:00:00 AMPCANC
Scheduled by a contractor via Hello! on 08/20/2002 at 11:07:41. Contact: ###-####. see added r/i 8/20/2002 6:26:31 PM
ELE02-02596 Electrical Rough-In8/20/20028/20/20028/20/2002 12:00:00 AMPPART
u/g ok