ELE02-02442
| Electrical Rough-In | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | FAIL |
|
|
###-#### 210.52(A) needs recept 2ft wall in new family rm, 250.148 grd outside light boxes, needs to check with structral on smoke detector locations? 8/20/2002 5:26:41 PM
|
ELE02-02523
| Final | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | PASS |
|
|
Scheduled by a contractor via Hello! on 08/19/2002 at 15:48:55. Contact: ###-####. ok 8/20/2002 10:59:56 AM
|
ELE02-02583
| Electrical Rough-In | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | FAIL |
|
|
GROUNDING ###-#### JOE cor. posted called 608.10 depht of pvc shall be 18 inches, also covered before inspection 8/20/2002 12:50:06 PM
|
ELE02-02165
| Electrical Rough-In | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | PART |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 07:11:39. Contact: ###-####. walls 8/20/2002 11:52:18 AM
|
ELE02-02559
| Electrical Rough-In | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | PASS |
|
|
DAN; Phone #: ###-#### both baths ok 8/20/2002 3:24:13 PM
|
ELE02-02580
| Electrical Rough-In | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | A | PART |
|
|
r/i and bond for inground spa ok 8/21/2002 10:54:10 AM
|
ELE02-02466
| Electrical Rough-In | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/19/2002 at 13:06:24. Contact: ###-####. u/g ok 8/20/2002 2:36:42 PM
|
ELE02-02367
| Electrical Rough-In | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PART |
|
|
###-#### john ceiling 8/20/2002 11:52:34 AM
|
ELE02-00325
| Final | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PASS |
|
|
CALL FIRST ###-#### KIM; Phone #: ###-####ok 8/19/2002 3:36:31 PM
|
ELE02-02580
| Final | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | NH |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 08:15:01. Contact: ###-####. called notice posted will do AM 08/21/02 8/20/2002 6:48:00 PM
|
ELE02-02582
| Permanent Service | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | FAIL |
|
|
###-#### cor. posted called 250.28 bond screw,250.52,or104 grd or bond water system, 250.90 bond nipple between meter and p/s disconnect, 250 53(D)(2) 2 grd rods 230.28 strap mast, 110.26 make sure panel has clearence and dedicated space 8/20/2002 3:48:19 PM
|
ELE02-01877
| Electrical Rough-In | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 08:47:57. Contact: ###-####. u/g for lights and electrode 8/20/2002 12:15:20 PM
|
ELE02-02528
| Rough-In Permanent Service | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 10:42:35. Contact: ###-####. called contractor said it is duplex prints say different called J Storey he will check on it need to meet with contractor 8/20/2002 6:05:32 PM
|
ELE02-02596
| Final | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 11:07:41. Contact: ###-####. see added r/i 8/20/2002 6:26:31 PM
|
ELE02-02596
| Electrical Rough-In | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PART |
|
|
u/g ok
|