FIR01-00596
| INSP-Conference | 8/16/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | CANC |
|
|
###-#### JEREMY canceled by Chris of Simplex 8/21/2002 8:09:32 AM
|
FIR02-00259
| INSP-Alarm Testing | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | CANC |
|
|
CHRIS; Phone #: ###-#### this phone number is for simplex; wrong permit number given 8/20/2002 2:57:35 PM
|
FIR02-00313
| INSP-Alarm Testing | 8/19/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | NR |
|
|
Scheduled by a contractor via Hello! on 08/19/2002 at 17:13:56. Contact: ###-####. Mark of Simplex said they weren't ready 8/21/2002 8:10:09 AM
|
FIR02-00272
| INSP-Supply line flush | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | PART |
|
|
Scheduled by a contractor via Hello! on 08/20/2002 at 08:04:58. Contact: ###-####. cover inspection for UG cover - okay to cover partial lay of new line; stubbed from street to within 10 feet of building; FDC is run in same trench and same distance from building 8/20/2002 10:17:53 AM
|
FIR02-00303
| INSP-Alarm Testing | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | FAIL |
|
|
###-#### plans don't match what is installed; devices don't match address on plans; need 75 cd strobes as shown on plans; move horn to 96 inches at south end due to shelf; update drawings 8/20/2002 3:10:21 PM
|
FIR02-00305
| INSP-Final Inspection | 8/20/2002 | 8/20/2002 | 8/20/2002 12:00:00 AM | P | FAIL |
|
|
met Tim (GC) and told him to get the work room sprinklered and that a hydro will be required
|