Inspections for the day of: Tuesday, August 20, 2002.
Number of inspections: 4
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
BLD02-00787 FIRE-Final Inspection8/19/20028/20/20028/20/2002 12:00:00 AMACANC
wrong inspection called for. the fire inspection has already been passed 8/20/2002 3:08:17 PM
BLD02-00645 FIRE-Final Inspection8/19/20028/20/20028/20/2002 12:00:00 AMAFAIL
duct detectors are mounted outside with no proof that they are listed for outdoor use. Contractor said they would provide the listing. Duct detectors still need to be tested 8/20/2002 12:14:14 PM
BLD02-00645 FIRE-Final Inspection8/19/20028/20/20028/20/2002 12:00:00 AMAFAIL
duct detectors are mounted outside with no proof that they are listed for outdoor use. Contractor said they would provide the listing. Duct detectors still need to be tested 8/20/2002 12:14:14 PM
FIR02-00217 INSP-Sprinkler Rough-in/Hydro8/19/20028/20/20028/20/2002 12:00:00 AMAPASS
System #3 aboveground hydro test OK but was witnessed by the general contractor. Roughin in gym and auditorium ok except for thru bolts are required for the EQ attachments to the brick walls 8/20/2002 4:06:20 PM