Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR03-00403 INSP-Sprinkler Rough-in/Hydro8/19/20038/20/20038/20/2003 12:00:00 AMAFAIL
###-#### harry Sprinkler rough-in failed. See approved plans for locations and items. Issues included hanging insulation, sprinklers overspaced, hangers on bottom chords of trusses. The undergroud supply piping is ok to cover. The hydro test is ok 8/20/2003 10:43:21 AM
BLD03-01459 FIRE-Final Inspection8/19/20038/20/20038/20/2003 12:00:00 AMAPASS
Life safety OK. Structural inspector to verify hardware on the rear exit door when installed 8/20/2003 11:00:35 AM
BLD03-01459 FIRE-Final Inspection8/19/20038/20/20038/20/2003 12:00:00 AMAPASS
Life safety OK. Structural inspector to verify hardware on the rear exit door when installed 8/20/2003 11:00:35 AM
BLD03-01459 FIRE-Final Inspection8/19/20038/20/20038/20/2003 12:00:00 AMAPASS
Life safety OK. Structural inspector to verify hardware on the rear exit door when installed 8/20/2003 11:00:35 AM
BLD02-01077 FIRE-Final Inspection8/20/20038/20/20038/20/2003 12:00:00 AMPFAIL
Provide annual inspection tags on the new fire extinguishers
BLD03-00366 FIRE-Final Inspection8/19/20038/20/20038/20/2003 12:00:00 AMPFAIL
matt ###-#### nac circuit not connected yet and the hvac units could not be put in heat mode for testing of the duct smoke detectors 8/20/2003 3:31:59 PM
FIR03-00214 INSP-Sprinkler Rough-in8/20/20038/20/20038/20/2003 12:00:00 AMPPART
###-#### sprinkler piping is ok to cover on the third floor. I notified Bruce with Commercial fire that the sprinkler pendants located in the furnace rooms will need to be changed to 175 degrees 8/20/2003 4:11:09 PM
FIR02-00360 INSP-Final Inspection8/20/20038/20/20038/20/2003 12:00:00 AMPPASS
Fire sprinklers finaled 8/20/2003 1:29:47 PM
FIR02-00196 INSP-Final Inspection8/20/20038/20/20038/20/2003 12:00:00 AMPPASS
Fire sprinkler finaled 8/20/2003 1:29:24 PM