ELE07-02764
| Final | 8/20/2007 | 8/20/2007 | 8/20/2007 2:47:29 PM | P | CANC |
|
|
Darrel; Phone #: ###-#### Internet Inspection Request from: Hattie James
|
ELE07-01936
| Final | 8/20/2007 | 8/20/2007 | 8/20/2007 2:19:49 PM | P | PART |
|
|
Call Boyd or Ted with any questions. At ###-#### Phone #: ###-#### Internet Inspection Request from: Daniel halls classrms, cafetteria ok
|
ELE06-04567
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 1:18:53 PM | P | FAIL |
|
|
Scheduled by a contractor via Hello! on 8/20/2007 at 6:44:30 AM. Contact: ###-####. corr. do not cover met owner, 314.16 box fill outside recept and jbox attic by closet door, 250.148 grd all metal boxes, 210.52(A) outlet spacing, 300.14 grd wires cut short , 110.14(B) all splices need a splicing means wires just twisted, note told owner to check manufactures instructions for location of smoke detector too close to vent?
|
ELE07-02016
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 12:30:22 PM | P | PASS |
|
|
On patio awning area. Randy''s cell ###-#### Phone #: ###-#### Internet Inspection Request from: Randy Fletcher ok
|
ELE07-00962
| Electrical Rough-In | 8/17/2007 | 8/20/2007 | 8/20/2007 10:50:27 AM | A | PASS |
|
|
Mike; Phone #: ###-#### Internet Inspection Request from: Hattie James r/i ok talked with owner on p/s that was bootlegged by prior owner has violations
|
ELE07-02080
| Electrical Rough-In | 8/17/2007 | 8/20/2007 | 8/20/2007 10:03:26 AM | A | PASS |
|
|
house, not garage; Eric; Phone #: ###-#### Internet Inspection Request from: Hattie James ok
|
ELE07-02882
| Final | 8/17/2007 | 8/20/2007 | 8/20/2007 9:11:11 AM | A | FAIL |
|
|
Tom ###-#### see added r/i
|
ELE07-02882
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 9:10:46 AM | A | FAIL |
|
|
Tom ###-#### 300.4 nail plates and 11/4" for cables parallel, remove devices so I can inspect makeup
|
ELE07-02846
| Rough-In Permanent Service | 8/18/2007 | 8/20/2007 | 8/20/2007 8:48:19 AM | A | PASS |
|
|
Phone #: ###-#### Internet Inspection Request from: Daryl DeGrange r/i p/s u/g new ok
|
ELE07-02458
| Rough-In Permanent Service | 8/17/2007 | 8/20/2007 | 8/20/2007 8:05:03 AM | A | DONE |
|
|
Gene; Phone #: ###-#### Internet Inspection Request from: Hattie James was done already
|
ELE07-02783
| Rough-In Permanent Service | 8/17/2007 | 8/20/2007 | 8/17/2007 12:00:00 AM | A | DONE |
|
|
Mike; reinspect; Phone #: ###-#### Internet Inspection Request from: Hattie James
|