ELE07-01676
| ELE-Aging Inspection | 8/20/2007 | 8/20/2007 | 8/21/2007 9:29:15 AM | | FAIL |
|
|
called to tell they need to comply with nec 300.11, raceway shall be supported at bottom of sign, they will call back
|
ELE07-01551
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 3:45:34 PM | P | PART |
|
|
Joe, 1st floor rooms only; Phone #: ###-#### Internet Inspection Request from: Cathy Weisshaupt 1st floor rooms anop ok to final
|
ELE07-00794
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 2:46:54 PM | P | CANC |
|
|
ceiling; hallways; Jesse; Phone #: ###-#### Internet Inspection Request from: Hattie James contractor called in wrong building
|
ELE07-02879
| Permanent Service | 8/20/2007 | 8/20/2007 | 8/20/2007 2:22:18 PM | P | FAIL |
|
|
Phil; Phone #: ###-#### Internet Inspection Request from: Hattie James called left corr notice, nec 250.52(A) metal water pipe entering building within 5' shall be used a part of grounding electrode system, 250.53(B) electrodes shall be minimum 6' apart, 250.53(G) electrodes shall be 8' long and flush with or below ground level, 110.3(A) shall not use metal romex connector for abrasion protection (plastic ok), Note: ground clamps shall br installed correctly 110.12(A) all unused openings shall be closed to afford protection equivalent to enclosure
|
ELE07-02872
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 1:37:29 PM | P | CANC |
|
|
###-#### - dustin
|
ELE07-02891
| Electrical Rough-In | 8/20/2007 | 8/20/2007 | 8/20/2007 12:31:03 PM | P | PASS |
|
|
jerod Phone #: ###-#### ric ok, called contr for 2 nail plates
|
ELE07-02620
| Permanent Service | 8/20/2007 | 8/20/2007 | 8/20/2007 10:20:12 AM | P | CANC |
|
|
Phone #: ###-#### Internet Inspection Request from: Celinda Winters Inspection cancelled from web by: Celinda Winters
|
ELE07-02884
| Electrical Rough-In | 8/17/2007 | 8/20/2007 | 8/20/2007 9:49:12 AM | A | PASS |
|
|
Jeremy ###-####//call for access ric ok
|
ELE06-03605
| Final | 8/20/2007 | 8/20/2007 | 8/20/2007 8:55:52 AM | A | PASS |
|
|
per call from contr, ok to final, nothing can be seen, airport mapping has identified
|
ELE07-02885
| Electrical Rough-In | 8/17/2007 | 8/20/2007 | 8/20/2007 8:54:09 AM | A | PART |
|
|
pat Phone #: ###-#### kitchen and utility room only ric ok, will call for big room ltr
|
ELE07-02866
| Rough-In Permanent Service | 8/17/2007 | 8/20/2007 | 8/20/2007 8:10:28 AM | A | PASS |
|
|
joe Phone #: ###-#### Internet Inspection Request from: Joseph Zumwalt ric ok, p/s u/g n ok
|
ELE07-02876
| Electrical Rough-In | 8/16/2007 | 8/20/2007 | 8/17/2007 10:50:00 AM | A | CANC |
|
|
pool bonding Phone #: ###-#### Internet Inspection Request from: Lee VanSchoiack Disp set to [CANC] by a contractor via Hello! on Aug 17 2007 10:50AM.
|