Inspections for the day of: Monday, August 20, 2007.
Number of inspections: 11
Percentage of inspections complete: 91 %
Percentage of inspections not complete: 9 %
Contact Information
InspectorForrest France
TitleFIRE INSPECTOR
Phone #794-1981
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR07-00124 FIR-Aging Inspection8/20/20078/20/20078/27/2007 11:02:08 AM DEFR
FIR07-00216 INSP-Final Inspection8/17/20078/20/20078/20/2007 3:54:52 PMPPASS
Fire alarm testing completed satisfactory, incorrect cd settings at two locations adjusted while on site, noted trouble on panel with an existing SD in the elevator mech. room to be repaired shortly per contractor, TI fire alarm permit finaled.
FIR07-00462 INSP-Final Inspection8/20/20078/20/20078/20/2007 3:47:04 PMPPASS
Fire alarm permit work passed final inspection, permit finaled.
FIR07-00667 INSP-Sprinkler Rough-in/Hydro8/20/20078/20/20078/20/2007 3:45:58 PMPPASS
Fire sprinkler permit finaled.
BLD06-03408 FIRE-Final Inspection8/20/20078/20/20078/20/2007 2:55:25 PMANR
Final pending satisfactory FA testing, on site conference regarding changes to EM lights as well.
FIR07-00474 INSP-Final Inspection8/17/20078/20/20078/20/2007 2:52:56 PMAPART
Functional testing of the preaction system only, remainder of OH work is not ready for final inspection.
FIR07-00599 INSP-Final Inspection8/16/20078/20/20078/20/2007 12:47:27 PMAFAIL
Noted items in need of correction on stamped plans including overspaced SD, missing horn/strobe, one strobe at the 2nd floor needs to be replaced, addressing on the first floor is incorrect, two SD on the 1st floor relocated while on site, one incorrect cd at a classroom adjusted while on site, need to provide as-builts reflecting field modifications,
FIR07-00715 INSP-Final Inspection8/17/20078/20/20078/20/2007 10:26:47 AMAFAIL
Wall-mounted visible notification appliance devices shall be installed per NFPA 72 2002 7.5.4.
FIR07-00667 INSP-Sprinkler Rough-in/Hydro8/20/20078/20/20078/20/2007 10:23:11 AMAPART
Fire sprinkler modifications are acceptable.
FIR07-00599 INSP-Final Inspection8/16/20078/20/20078/16/2007 12:44:24 PMPCANC
Scheduled by a contractor via Hello! on 8/16/2007 at 12:29:19 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Aug 16 2007 12:44PM.
BLD03-02347 Extend Permit 180 days8/20/20078/20/2007 P