FIR07-00124
| FIR-Aging Inspection | 8/20/2007 | 8/20/2007 | 8/27/2007 11:02:08 AM | | DEFR |
|
|
|
FIR07-00216
| INSP-Final Inspection | 8/17/2007 | 8/20/2007 | 8/20/2007 3:54:52 PM | P | PASS |
|
|
Fire alarm testing completed satisfactory, incorrect cd settings at two locations adjusted while on site, noted trouble on panel with an existing SD in the elevator mech. room to be repaired shortly per contractor, TI fire alarm permit finaled.
|
FIR07-00462
| INSP-Final Inspection | 8/20/2007 | 8/20/2007 | 8/20/2007 3:47:04 PM | P | PASS |
|
|
Fire alarm permit work passed final inspection, permit finaled.
|
FIR07-00667
| INSP-Sprinkler Rough-in/Hydro | 8/20/2007 | 8/20/2007 | 8/20/2007 3:45:58 PM | P | PASS |
|
|
Fire sprinkler permit finaled.
|
BLD06-03408
| FIRE-Final Inspection | 8/20/2007 | 8/20/2007 | 8/20/2007 2:55:25 PM | A | NR |
|
|
Final pending satisfactory FA testing, on site conference regarding changes to EM lights as well.
|
FIR07-00474
| INSP-Final Inspection | 8/17/2007 | 8/20/2007 | 8/20/2007 2:52:56 PM | A | PART |
|
|
Functional testing of the preaction system only, remainder of OH work is not ready for final inspection.
|
FIR07-00599
| INSP-Final Inspection | 8/16/2007 | 8/20/2007 | 8/20/2007 12:47:27 PM | A | FAIL |
|
|
Noted items in need of correction on stamped plans including overspaced SD, missing horn/strobe, one strobe at the 2nd floor needs to be replaced, addressing on the first floor is incorrect, two SD on the 1st floor relocated while on site, one incorrect cd at a classroom adjusted while on site, need to provide as-builts reflecting field modifications,
|
FIR07-00715
| INSP-Final Inspection | 8/17/2007 | 8/20/2007 | 8/20/2007 10:26:47 AM | A | FAIL |
|
|
Wall-mounted visible notification appliance devices shall be installed per NFPA 72 2002 7.5.4.
|
FIR07-00667
| INSP-Sprinkler Rough-in/Hydro | 8/20/2007 | 8/20/2007 | 8/20/2007 10:23:11 AM | A | PART |
|
|
Fire sprinkler modifications are acceptable.
|
FIR07-00599
| INSP-Final Inspection | 8/16/2007 | 8/20/2007 | 8/16/2007 12:44:24 PM | P | CANC |
|
|
Scheduled by a contractor via Hello! on 8/16/2007 at 12:29:19 PM. Contact: ###-####. Disp set to [CANC] by a contractor via Hello! on Aug 16 2007 12:44PM.
|
BLD03-02347
| Extend Permit 180 days | 8/20/2007 | 8/20/2007 | | P | |
|
|
|