Inspections for the day of: Wednesday, August 20, 2008.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorBob Reichert
TitleELE-INSPECTOR
Phone #794-1923
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE08-01647 Final8/20/20088/20/20088/20/2008 3:58:30 PMPPASS
jim Phone #: ###-#### ok to final signed occupancy card, no esc this project
ESC07-01472 General Inspection8/20/20088/20/20088/20/2008 3:15:30 PMPPART
looked ok
ESC08-00480 General Inspection8/20/20088/20/20088/20/2008 3:13:25 PMPPART
looked ok
ELE08-02244 Rough-In Permanent Service8/20/20088/20/20088/20/2008 2:47:51 PMPPASS
Alan Phone #: ###-#### ri ok, left survey, called contractor, BCC 4-05-33(A),(B) sprinkler control shall be listed by a nationally recognized testing laboratory, p/s u/g n ok
ELE08-01648 Final8/20/20088/20/20088/20/2008 1:37:35 PMPPASS
jim Phone #: ###-#### ok to final, signed occupancy card, no esc this project
ELE08-02208 Electrical Rough-In8/19/20088/20/20088/20/2008 12:39:24 PMPCANC
Dale Phone #: ###-#### see conference
ELE08-02208 Conference8/20/20088/20/20088/20/2008 12:38:49 PMPDONE
Dale Phone #: ###-#### talked with electrical contractor about being ready for inspection, doing in parts for u/g because of depth and sluff box, conduit spacers side by side and top cover row, meters at transformer, but contractor doing work up to disconnects inside building, so city will inspect, general calling in inspections, so electrical contractor will have to co-ordinate when inspection to be requested
ELE08-02318 Rough-In Permanent Service8/19/20088/20/20088/20/2008 10:31:33 AMAPASS
#80689,Q#8231AXK. WIRED A NEW POWER PEDESTAL & NEW PHONE CABINET FOR QWEST. BRIAN ###-####. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell p/s u/g n ok, no esc this project
ELE08-02323 Final8/19/20088/20/20088/20/2008 10:05:31 AMAFAIL
WAYNE nOTE: PLEASE CALL 1/2 HR PRIOR TO INSPECTION Phone #: ###-#### met electrician, left correction notice, NEC 400.8 flexible cord shall not be used as a substitute for fixed wiring or where subject to physical damage,110.3 and BCC 4-05-33(A)&(B) all equipment shall be listed by a nationally recognized testing laboratory, NOTE: cottections shall be made within 10 days or further action will be taken such as removal of power
ELE08-01848 Electrical Rough-In8/19/20088/20/20088/20/2008 9:08:09 AMAPART
luke - sitting room at baby gap - ceiling Phone #: ###-#### ok cover ceiling kids sitting room and baby ceilings, no esc this project
ELE08-02317 Rough-In Permanent Service8/19/20088/20/20088/20/2008 8:32:45 AMAPASS
#80691,Q#8231AWR. Wired a new power pedestal & phone cabinet for QWEST. James ###-####. Phone #: ###-#### Internet Inspection Request from: Dan Mitchell p/s u/g n ok, no esc this project
ELE08-00459 Permanent Service8/19/20088/20/20088/20/2008 8:04:06 AMAFAIL
Scheduled by a contractor via Hello! on 8/19/2008 at 11:47:47 AM. Contact: ###-####. called, left correction notice, NEC 404.8 center of grip of operating handle shall not be over 6'-7" above floor, 110.22 disconnects shall be labelled to indicate its purpose and be of sufficient durability to withstand its environment, 250.68 connection to grounding electrode shall be accessible, 358.30(A) shall strap emt within 3' of box,250.52 shall provide concrete encased electrode, BCC shall provide separate electrical permit for 2nd meter