Inspections for the day of: Wednesday, August 20, 2008.
Number of inspections: 9
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR08-00528 INSP-Final Inspection8/20/20088/20/20088/20/2008 4:31:55 PMPFAIL
The new duct smoke detector had not been wired to the facp yet and the monitoring company had not been set up for the new zone. Also the plastic sample tube in the duct smoke detector needed to be removed and the steel tube put in its position. No inspection was performed for function.
FIR08-00487 INSP-Supply line flush8/20/20088/20/20088/20/2008 4:29:05 PMPCANC
To be canceled per Jeremy. This is an underground flush. Jeremy is the contact. Thanks Phone #: ###-####
FIR08-00487 INSP-Sprinkler Rough-in/Hydro8/20/20088/20/20088/20/2008 4:28:24 PMPCANC
To be canceled per Jeremy. This is an underground hydro Phone #: ###-####
FIR08-00560 INSP-Sprinkler Rough-in/Hydro8/19/20088/20/20088/20/2008 4:26:31 PMPPASS
The two additional upright heads have been added both restroom sprinkler piping can be covered.
FIR08-00519 INSP-Final Inspection8/20/20088/20/20088/20/2008 2:05:27 PMPPASS
Permit finaled
BLD08-01166 FIRE-Final Inspection8/19/20088/20/20088/20/2008 1:27:02 PMAPASS
fire life safety passed. This inspection required two trips since the pocket door hardware was incorrect and the suite number was not installed on the first trip.
FIR08-00549 INSP-Final Inspection8/20/20088/20/20088/20/2008 12:40:01 PMPPASS
Permit finaled
FIR08-00433 INSP-Sprinkler Rough-in8/19/20088/20/20088/20/2008 12:02:07 PMAPART
The 8" stub out is ok to bury. The remaining underground piping to be inspected when complete.
BLD08-01771 FIRE-Final Inspection8/19/20088/20/20088/20/2008 9:45:01 AMAPART
A temporary occupancy was given until the suite number is provided and the exit sign is either repaired or removed.