Inspections for the day of: Thursday, August 20, 2009.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorTroy Cobbley
TitleFIRE INSPECTOR
Phone #794-9483
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
FIR09-00429 INSP-Final Inspection8/20/20098/20/20098/25/2009 4:10:55 PMPCANC
Cancelled per Tim Christopherson.
FIR09-00317 INSP-Sprinkler Rough-in8/19/20098/20/20098/21/2009 11:45:45 AMAPART
Inspected system 2 piping in the attic for the protection of the ground floor. Everything seemed ok except for the hanger situation which was added as a separate activity in the case file.

Inspected system 3 for proper sprinkler coverage. Most of the system was ok. Some areas were not complete and marked in red indicated by NR (Not Reviewed) on the job site plans.

Inspected the new addition for cover. All seemed ok except for the door ways leading into the new area. There were doors leading into this area that blocked coverage from the sidewall sprinklers in the gym for the doorways. I was informed that the doors were to be removed. If the doors are not removed than additional sprinklers will be required in both doorways.

BLD09-01008 FIRE-Final Inspection8/20/20098/20/20098/21/2009 11:29:48 AMPPASS
Life safety passed
FIR09-00454 INSP-Final Inspection8/20/20098/20/20098/21/2009 9:36:50 AMPPASS
permit finaled
FIR09-00410 INSP-Final Inspection8/20/20098/20/20098/20/2009 4:57:20 PMPFAIL
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
FIR09-00411 INSP-Final Inspection8/20/20098/20/20098/20/2009 4:56:41 PMPFAIL
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
FIR09-00409 INSP-Final Inspection8/20/20098/20/20098/20/2009 4:55:38 PMPFAIL
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
FIR09-00352 INSP-Final Inspection8/20/20098/20/20098/20/2009 4:54:05 PMPFAIL
Signals were received by central station but the fire alarm panel did not latch on alarm and reset by itself. Also the the netcom was a 6.
FIR09-00449 INSP-Supply line flush8/18/20098/20/20098/20/2009 12:28:24 PMAPASS
The underground supply hydro test and flush passed inspection. Also mark sentenno has approved the location of the PIV.
FIR09-00381 INSP-Alarm Testing8/20/20098/20/20098/20/2009 12:16:28 PMPPASS
The kitchen area and three nearby offices, as marked on the city approved plans, tested ok.
BLD07-01834 FIRE-Final Inspection8/18/20098/20/20098/20/2009 12:15:52 PMAPART
The kitchen area and three nearby offices, as marked on the city approved plans, is ok to occupy.
FIR09-00436 INSP-Final Inspection8/19/20098/20/20098/20/2009 12:08:43 PMAPASS
Permit finaled
FIR09-00331 FIR-Aging Inspection8/20/20098/20/20098/20/2009 10:29:08 AM NR
work is in progress
FIR09-00414 INSP-Final Inspection8/19/20098/20/20098/20/2009 9:31:29 AMAPASS
Permit finaled