FIR09-00429
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/25/2009 4:10:55 PM | P | CANC |
|
|
Cancelled per Tim Christopherson.
|
FIR09-00317
| INSP-Sprinkler Rough-in | 8/19/2009 | 8/20/2009 | 8/21/2009 11:45:45 AM | A | PART |
|
|
Inspected system 2 piping in the attic for the protection of the ground floor. Everything seemed ok except for the hanger situation which was added as a separate activity in the case file. Inspected system 3 for proper sprinkler coverage. Most of the system was ok. Some areas were not complete and marked in red indicated by NR (Not Reviewed) on the job site plans. Inspected the new addition for cover. All seemed ok except for the door ways leading into the new area. There were doors leading into this area that blocked coverage from the sidewall sprinklers in the gym for the doorways. I was informed that the doors were to be removed. If the doors are not removed than additional sprinklers will be required in both doorways.
|
BLD09-01008
| FIRE-Final Inspection | 8/20/2009 | 8/20/2009 | 8/21/2009 11:29:48 AM | P | PASS |
|
|
Life safety passed
|
FIR09-00454
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/21/2009 9:36:50 AM | P | PASS |
|
|
permit finaled
|
FIR09-00410
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 4:57:20 PM | P | FAIL |
|
|
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
|
FIR09-00411
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 4:56:41 PM | P | FAIL |
|
|
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
|
FIR09-00409
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 4:55:38 PM | P | FAIL |
|
|
I arrived on site and was notified by TIm that the netcom rating was not a 5 or less. No inspection was not continued.
|
FIR09-00352
| INSP-Final Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 4:54:05 PM | P | FAIL |
|
|
Signals were received by central station but the fire alarm panel did not latch on alarm and reset by itself. Also the the netcom was a 6.
|
FIR09-00449
| INSP-Supply line flush | 8/18/2009 | 8/20/2009 | 8/20/2009 12:28:24 PM | A | PASS |
|
|
The underground supply hydro test and flush passed inspection. Also mark sentenno has approved the location of the PIV.
|
FIR09-00381
| INSP-Alarm Testing | 8/20/2009 | 8/20/2009 | 8/20/2009 12:16:28 PM | P | PASS |
|
|
The kitchen area and three nearby offices, as marked on the city approved plans, tested ok.
|
BLD07-01834
| FIRE-Final Inspection | 8/18/2009 | 8/20/2009 | 8/20/2009 12:15:52 PM | A | PART |
|
|
The kitchen area and three nearby offices, as marked on the city approved plans, is ok to occupy.
|
FIR09-00436
| INSP-Final Inspection | 8/19/2009 | 8/20/2009 | 8/20/2009 12:08:43 PM | A | PASS |
|
|
Permit finaled
|
FIR09-00331
| FIR-Aging Inspection | 8/20/2009 | 8/20/2009 | 8/20/2009 10:29:08 AM | | NR |
|
|
work is in progress
|
FIR09-00414
| INSP-Final Inspection | 8/19/2009 | 8/20/2009 | 8/20/2009 9:31:29 AM | A | PASS |
|
|
Permit finaled
|