Inspections for the day of: Friday, August 20, 2010.
Number of inspections: 13
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorJack Frank
TitleELE-INSPECTOR
Phone #794-1930
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01811 Final8/20/20108/20/20108/24/2010 11:45:25 AMPCANC
ELE10-01830 Permanent Service8/20/20108/20/20108/20/2010 2:32:57 PMPPASS
p/s o/h rec. ok
ELE10-01766 Final8/20/20108/20/20108/20/2010 2:31:42 PMPPASS
bill Phone #: ###-####
ELE10-01495 Final8/20/20108/20/20108/20/2010 2:31:25 PMPPASS
Please contact Don Crane at ###-#### Phone #: ###-#### >> Inspection requested via web by Deb Gooden
ELE10-01777 Final8/20/20108/20/20108/20/2010 2:31:07 PMPPART
please call around noon to let us know about what time you''ll be there.. we''d like to stick around to cover the pipe after you''ve inspected. thanks! Phone #: ###-####
>> Inspection requested via web by CINDY BIXLER see added request
ELE10-01829 Permanent Service8/20/20108/20/20108/20/2010 2:29:43 PMPFAIL
warren Phone #: ###-#### called correction posted 230.24(A) needs 8ft over roof, 230.28 shall provide guy kit or stiffleg ,that opposes strain of service drop, check for 2 grd rods and grd or bond water system
ELE10-01811 Final8/19/20108/20/20108/20/2010 12:59:02 PMAFAIL
Mike or ###-#### homeowner Phone #: ###-#### called bond soffit vent #8 bond shall terminate at spa equipment , , check outside fixture 5ft above water level
ELE10-01811 Electrical Rough-In8/20/20108/20/20108/20/2010 12:55:48 PMAPART
Mike or ###-#### homeowner Phone #: ###-####
ELE10-01802 Temporary Service8/19/20108/20/20108/20/2010 12:55:02 PMAFAIL
Greg is the contact his no. is ###-####. Phone #: ###-#### >> Inspection requested via web by Shawna Gates
drive grd rod flush WR recepts
ELE10-01801 Temporary Service8/19/20108/20/20108/20/2010 12:53:59 PMAFAIL
Greg is the contact his cell no. is ###-#### Phone #: ###-#### >> Inspection requested via web by Shawna Gates drive grd rod, cord to job trailer needs to be rated for 100 amp also needs 100 amp breaker, WR recepts and inuse covers called
ELE10-01751 Electrical Rough-In8/19/20108/20/20108/20/2010 11:57:34 AMAPASS
Phone #: ###-#### >> Inspection requested via web by Bryan Atkins new high ceiling
ELE10-01495 Final8/19/20108/20/20108/20/2010 11:57:03 AMANR
Contact: Don Crane Phone #: ###-#### >> Inspection requested via web by Deb Gooden
ELE10-01777 Permanent Service8/20/20108/20/20108/20/2010 11:56:40 AMAPASS
p/s o/h new ok