Inspections for the day of: Wednesday, August 20, 2014.
Number of inspections: 12
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE12-00913 ELE-Aging Inspection8/20/20148/20/20148/21/2014 8:03:07 AM DONE
too busy
ELE12-02301 ELE-Aging Inspection8/20/20148/20/20148/21/2014 8:01:48 AM DONE
too busy
ELE14-02302 Electrical Rough-In8/20/20148/20/20148/20/2014 4:32:44 PMPPASS
Underground: (2) pool lights, (1) spa light, (1) autocover, ; (1) equipment feed
Bonding: (2) Autocover, (1) Rain gutter, (1) pool light, (1) Pool/spa equipment, (1) Pool/spa panel Phone #: ###-#### Inspection requested via web by Lars Johnson r/i ok u. ground and bonding
ELE14-02259 Temporary Service8/20/20148/20/20148/20/2014 4:07:03 PMPPASS
temp pole Phone #: ###-#### Inspection requested via web by Stephen Kren t/s u/g n ok
ELE14-01849 Electrical Rough-In8/20/20148/20/20148/20/2014 3:55:09 PMPPASS
Phone #: ###-#### Inspection requested via web by Kerri Hamilton 8th floor east window walls r/i ok
ELE14-02218 Rough-In Permanent Service8/20/20148/20/20148/20/2014 3:24:25 PMPCANC
Please call Dave if any defects noted Phone #: ###-#### Inspection requested via web by David Mackey needed p/s failed r/i
ELE14-02218 Electrical Rough-In8/20/20148/20/20148/20/2014 3:15:41 PMPFAIL
Please call Dave if any defects noted Phone #: ###-#### Inspection requested via web by David Mackey Underground subfeed to house never inspected . 334.30-nm cable in garage not secured. need straps on riser and underground raceway. 300.4-need 11/4" from edge of bored holes to nearest edge of wood member for nm cable . Bsmt. furred walls included (see list of areas). Need conv. outlet in hall 10' long (near top of stairs to back of house.) 250.32-Separate buildings supplied by feeder needs grounding electrode.
ELE14-02218 Permanent Service8/20/20148/20/20148/20/2014 3:00:56 PMPPASS
Please call Dave if any defects noted Phone #: ###-#### Inspection requested via web by David Mackey p/s o/h n ok
ELE14-00629 Final8/20/20148/20/20148/20/2014 2:13:13 PMPPASS
please call first-Larry Phone #: ###-#### final ok
GCE14-00100 GCE-Rough-In Permanent Service8/20/20148/20/20148/20/2014 12:52:12 PMPPASS
(Mandatory Inspection)-contact ###-#### p/s u/g n ok r/i ok
ELE13-02328 ELE-Request for Extension8/19/20148/20/20148/20/2014 12:10:11 PMAPASS
Kevin-###-#### extension granted
ELE14-01882 Final8/20/20148/20/20148/20/2014 8:28:36 AMAPASS
Danny Is the contact. Phone #: ###-#### Inspection requested via web by Buster Bowen final ok