BLD14-01495
| FIRE-Final Inspection | 8/19/2014 | 8/20/2014 | 8/20/2014 3:22:41 PM | P | CANC |
|
|
Performed a conference with the contractor. He will call and reschedule when ready.
|
FIR14-00592
| INSP-Sprinkler Rough-in | 8/20/2014 | 8/20/2014 | 8/20/2014 3:21:58 PM | P | PASS |
|
|
Rough-in passed. Don stated that a soffit is going to be installed between the two side wall heads
|
FIR14-00544
| INSP-Sprinkler Rough-in | 8/20/2014 | 8/20/2014 | 8/20/2014 3:19:43 PM | P | FAIL |
|
|
Left message on contacts voice mail.No contact on site. Arrived on site, no and no approved plans were available and the piping has not been installed at the minumum 4'-6" depth.
|
FIR14-00417
| INSP-Sprinkler Rough-in | 8/20/2014 | 8/20/2014 | 8/20/2014 2:22:55 PM | P | PASS |
|
|
Underground supply is ok to cover
|
BLD14-00925
| FIRE-Final Inspection | 8/19/2014 | 8/20/2014 | 8/20/2014 2:22:33 PM | A | FAIL |
|
|
Life safety will be ok to pass when the existing fire alarm has been extended into the new area.
|
GCB14-00090
| FIRE-Final Inspection | 8/20/2014 | 8/20/2014 | 8/20/2014 2:21:49 PM | P | PASS |
|
|
life safety passed
|
BLD12-03330
| FIRE-Final Inspection | 8/18/2014 | 8/20/2014 | 8/20/2014 2:11:04 PM | A | PASS |
|
|
life safety passed
|
FIR14-00098
| INSP-Final Inspection | 8/20/2014 | 8/20/2014 | 8/20/2014 2:07:37 PM | P | PASS |
|
|
Permit finaled
|
FIR14-00354
| INSP-Sprinkler Rough-in | 8/19/2014 | 8/20/2014 | 8/20/2014 10:20:48 AM | A | PART |
|
|
Rough-in passed for System 1 (east & west) except plan modification is needed showing the additional branchline in the remote area and pipe size changes. Rough-in passed for Systems 2 and 4. System 3 has not been inspected yet. Risers have not been inspect yet.
|
BLD14-02237
| FIRE-Final Inspection | 8/19/2014 | 8/20/2014 | 8/20/2014 10:16:17 AM | A | PASS |
|
|
life safety passed
|
FIR14-00427
| INSP-Final Inspection | 8/19/2014 | 8/20/2014 | 8/20/2014 9:48:00 AM | A | PASS |
|
|
Permit finaled
|
FIR14-00427
| INSP-Sprinkler Rough-in | 8/19/2014 | 8/20/2014 | 8/20/2014 9:47:42 AM | A | PASS |
|
|
Rough-in passed
|
BLD14-01614
| FIRE-Final Inspection | 8/18/2014 | 8/20/2014 | 8/20/2014 8:22:25 AM | A | PART |
|
|
A temporary occupancy is being given with scott's permission until the project related fire alarm permit is finaled
|
BLD14-01615
| FIRE-Final Inspection | 8/18/2014 | 8/20/2014 | 8/20/2014 8:19:41 AM | A | PART |
|
|
A temporary occupancy is given with scott's approval until the project related fire alarm permit has been finaled
|