Inspections for the day of: Thursday, August 20, 2015.
Number of inspections: 11
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorRex Boyles
TitleELE-INSPECTOR
Phone #685-9023
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
ELE10-01638 ELE-Aging Inspection8/20/20158/20/20158/25/2015 2:59:04 PM DONE
no contact number
ELE11-02430 ELE-Aging Inspection8/20/20158/20/20158/25/2015 9:16:45 AM DONE
laura will try to final
ELE15-01257 Electrical Rough-In8/19/20158/20/20158/20/2015 2:24:58 PMPPASS
Ceiling Cover. Von is the onsite contact. Phone #: ###-#### Inspection requested via web by Buster Bowen r/i t grid ceilings ok Robert will leave tiles out where j boxes need to be made up
ELE15-02271 Electrical Rough-In8/20/20158/20/20158/20/2015 1:45:27 PMPPASS
Call 30 mins before // Larry Phone #: ###-#### r/i ok
ELE15-02447 Rough-In Permanent Service8/20/20158/20/20158/20/2015 1:15:15 PMPPASS
Phone #: ###-#### Inspection requested via web by Lynn Cable corrections made r/i ok p/s u/g n ok
ELE15-02619 Temporary Service8/20/20158/20/20158/20/2015 11:08:44 AMAPASS
Phone #: ###-#### Inspection requested via web by TOM BICANDI t/s u/g n ok
ELE15-01910 Final8/19/20158/20/20158/20/2015 10:20:29 AMAFAIL
Dan ###-#### Inspection requested via web by Dan Hobdey 422.31(B)- disconnect required in sight or lockoff on circuit breaker required.
ELE15-02447 Electrical Rough-In8/20/20158/20/20158/20/2015 10:03:43 AMPCANC
Phone #: ###-#### >> Inspection requested via web by Lynn Cable Inspection cancelled from web by: Lynn Cable
ELE15-02618 Electrical Rough-In8/19/20158/20/20158/20/2015 10:02:59 AMAPASS
Access project through side gate, then go in the back door Phone #: ###-#### Inspection requested via web by Brad Girard r/i kit ok
ELE15-00842 Electrical Rough-In8/19/20158/20/20158/20/2015 9:23:21 AMAPASS
Phone #: ###-#### Inspection requested via web by Mark M r/i ok all t grid ceiling ok to cover
ELE15-02613 Final8/19/20158/20/20158/20/2015 8:46:26 AMAFAIL
The GC has requested we have the inspection as early as possible so he can get his building inspector in there next. Thanks for anything you can do. Our electrician contact is Julian ###-#### or Alex ###-####. Thanks again. Phone #: ###-#### Inspection requested via web by Clint Tate 300.11-identify seismic on troffers. 760.41(A)- fire alarm dedicated circuit shall be secured in the on position with lockoff. 760.41(B)- fire alarm circuit disconnect shall have red identfication.