Inspections for the day of: Tuesday, August 21, 2001.
Number of inspections: 14
Percentage of inspections complete: 100 %
Percentage of inspections not complete: 0 %
Contact Information
InspectorAlan Hauser
TitleMEC-COM/RES INSPECTOR
Phone #794-9453
Permit NumberDescriptionReceivedRequestedCompletedAM/PMDisposition 
MEC01-01700 MEC-Aging Inspection8/21/20018/21/20018/21/2001 12:00:00 AM FAIL
MEC01-01526 MEC-Aging Inspection8/21/20018/21/20018/21/2001 12:00:00 AM FAIL
MEC01-02187 Rough-in8/20/20018/21/20018/21/2001 12:00:00 AMAPASS
Scheduled by a contractor via Hello! on 08/20/2001 at 12:58:41. Contact: ###-####.
MEC01-02286 Rough-in8/20/20018/21/20018/21/2001 12:00:00 AMAPASS
south 2 floors looked at, this should be whole bldg. now looked at 8/21/2001 12:03:23 PM
MEC01-01586 Rough-in8/20/20018/21/20018/21/2001 12:00:00 AMAPART
east end ok, no inspection in deli area of hoods 8/21/2001 10:56:51 AM
MEC01-02434 Pressure Test8/20/20018/21/20018/21/2001 12:00:00 AMAPASS
kurt ###-####
MEC01-02497 Rough-in8/21/20018/21/20018/21/2001 12:00:00 AMAPASS
###-#### kay
MEC01-02462 Rough-in8/21/20018/21/20018/21/2001 12:00:00 AMPPART
still need comb air to outdoors not crawlspace, check on final, crawlspace installation approved by #411, pt ok, no inspection of piping approved by #411 8/21/2001 1:14:43 PM
MEC01-00944 Conference8/21/20018/21/20018/21/2001 12:00:00 AMPPASS
PROFIT Mtg. today @ 1:30
MEC01-01449 Final8/21/20018/21/20018/21/2001 12:00:00 AMPPASS
Scheduled by a contractor via Hello! on 08/21/2001 at 09:55:46. Contact: ###-####.
MEC01-01861 Rough-in8/21/20018/21/20018/21/2001 12:00:00 AMPPART
duct ok, no grid or unit heaters hung 8/21/2001 3:58:01 PM
MEC01-02463 Rough-in8/21/20018/21/20018/21/2001 12:00:00 AMPPASS
###-#### bill
MEC01-02463 Pressure Test8/21/20018/21/20018/21/2001 12:00:00 AMPPASS
###-#### bill
MEC01-00763 Final8/21/20018/21/20018/21/2001 12:00:00 AMPFAIL
Added by Inspector: 350 On 8/21/2001 12:27:32 PM gasline undersized at rtu, raise regulator vent